NOTES
Priority control with LR 1-A
2
1
1 Control cable to the contactor of the second appliance (e.g.
electric storage heater).
2 Control contact opens when switching the instantaneous
water heater on.
16.3 DHW output
The DHW output is subject to the mains voltage, the appliance's
connected load and the cold water inlet temperature. The rated
voltage and rated output can be found on the type plate (see
chapter "Operation / Troubleshooting").
Connected load in kW
38 °C DHW output in l/min.
Rated voltage
Cold water inlet temperature
380 V
400 V
415 V
10.1
11.0
12.0
12.2
13.2
13.5
13.6
14.2
14.5
15.0
16.2
16.3
18.0
19.0
19.4
21.0
21.7
22.6
23.5
24.0
24.4
25.8
26.0
27.0
36
| DHB-E SLi
5 °C
10 °C
15 °C
20 °C
4.4
5.2
6.3
4.8
5.6
6.8
5.2
6.1
7.5
5.3
6.2
7.6
5.7
6.7
8.2
10.5
5.8
6.9
8.4
10.7
5.9
6.9
8.4
10.8
6.1
7.2
8.8
11.3
6.3
7.4
9.0
11.5
6.5
7.7
9.3
11.9
7.0
8.3
10.1
12.9
7.1
8.3
10.1
12.9
7.8
9.2
11.2
14.3
8.2
9.7
11.8
15.1
8.4
9.9
12.0
15.4
9.1
10.7
13.0
16.7
9.4
11.1
13.5
17.2
9.8
11.5
14.0
17.9
10.2
12.0
14.6
18.7
10.4
12.2
14.9
19.0
10.6
12.4
15.2
19.4
11.2
13.2
16.0
20.5
11.3
13.3
16.1
20.6
11.7
13.8
16.8
21.4
Connected load in kW
Rated voltage
380 V
400 V
10.1
11.0
12.0
12.2
13.2
13.5
13.6
15.0
16.2
16.3
18.0
19.0
21.0
21.7
23.5
24.0
24.4
26.0
27.0
8.0
16.4 Application areas / conversion table
8.7
9.5
Specific electrical resistance and specific electrical conductivity
9.7
(see chapter "Installation / Data table").
Standard specifica-
tion at 15 °C
Conductivity σ ≤ Resist-
Resist-
ance
ρ ≥
Ωcm
mS/m μS/cm
900
111
1111
1000
100
1000
1100
91
909
1200
83
833
1300
77
769
16.5 Pressure drop
Taps/valves
Tap pressure drop at a flow rate of 10 l/min
Mono lever mixer tap, approx.
Thermostatic valve, approx.
Shower head, approx.
Sizing the pipework
When calculating the size of the pipework, an appliance pressure
drop of 0.1 MPa is recommended.
16.6 Fault conditions
In the event of a fault, loads up to a maximum of 95 °C at a pres-
sure of 1.2 MPa can occur temporarily in the installation.
50 °C DHW output in l/min.
Cold water inlet temperature
415 V
5 °C
10 °C
3.2
3.6
3.5
3.9
3.8
4.3
3.9
4.4
4.2
4.7
4.3
4.8
4.3
4.9
14.2
4.5
5.1
14.5
4.6
5.2
4.8
5.4
5.1
5.8
5.2
5.8
5.7
6.4
6.0
6.8
19.4
6.2
6.9
6.7
7.5
6.9
7.8
22.6
7.2
8.1
7.5
8.4
7.6
8.6
7.7
8.7
25.8
8.2
9.2
8.3
9.3
8.6
9.6
20 °C
25 °C
Conductivity σ ≤ Resist-
ance
ance
ρ ≥
ρ ≥
Ωcm
mS/m μS/cm
Ωcm
800
125
1250
735
890
112
1124
815
970
103
1031
895
1070
93
935
985
1175
85
851
1072
MPa
MPa
MPa
www.stiebel-eltron.com
15 °C
20 °C
4.1
4.8
4.5
5.2
4.9
5.7
5.0
5.8
5.4
6.3
5.5
6.4
5.6
6.5
5.8
6.8
5.9
6.9
6.1
7.1
6.6
7.7
6.7
7.8
7.3
8.6
7.8
9.0
7.9
9.2
8.6
10.0
8.9
10.3
9.2
10.8
9.6
11.2
9.8
11.4
10.0
11.6
10.5
12.3
10.6
12.4
11.0
12.9
Conductivity σ ≤
mS/m
μS/cm
136
1361
123
1227
112
1117
102
1015
93
933
0.04 - 0.08
0.03 - 0.05
0.03 - 0.15