ENGLISH
- set the function selector to winter mode
- remove the housing and access the card
- insert the jumpers JP1 and JP2
- use a screwdriver to prise open the plug on the control panel
- bring the trimmer P2 to the maximum value, using a screwdriver
(turn clockwise)
- remove the screw of the combustion analysis inlet cover (fi g. 18)
and insert the probes
- power the boiler
The appliance works at maximum output and it is possible to check
combustion.
After analysis is complete:
- close the hot water tap
- remove the probe from the analyser and close the combustion
analysis inlet fastening carefully the screw previously removed.
10
USER
1A GENERAL WARNINGS
The instruction manual is an integral part of the product and it must
therefore be kept carefully and must accompany the appliance; if
the manual is lost or damaged, another copy must be requested
from the Technical Assistance Service.
Boiler installation and any other assistance and maintenance
operation must be carried out by qualifi ed personnel accord-
ing to current local and national regulations.
For installation, it is advisable to contact specialised personnel.
The boiler must only be used for the application foreseen by
the manufacturer. The manufacturer shall not be liable for
any damage to persons, animals or property due to errors in
installation, calibration, maintenance or due to improper use.
The safety and automatic adjustment devices must not be
modifi ed, during the system life cycle, by the manufacturer
or supplier.
This appliance produces hot water, therefore it must be con-
nected to a heating system and/or a domestic hot water
mains, compatible with its performance and output.
In case of water leakage, close the water supply and contact
the Technical Assistance Service immediately.
In case of absence for long periods time, close the gas sup-
ply and switch off the electrical supply main switch. In case
of risk of frost, empty the boiler.
From time to time check that the operating pressure of the
hydraulic system does not decrease under 1 bar.
In case of failure and/or malfunctioning, deactivate the appli-
ance, and do not try to repair or intervene directly on it.
Appliance maintenance must be carried out at least once a
year: program it with the Technical Assistance Service will
avoid wasting time and money.
C.A.I. models: the ventilation openings are vital for correct
combustion.
Boiler use requires to strictly observe some basic safety rules:
Do not use the appliance in any manner other than its in-
tended purpose.
It is dangerous to touch the appliance with wet or damp body
parts and/or in bare feet.
Under no circumstances cover the intake grids, dissipa-
tion grids and ventilation vents in the installation room with
cloths, paper or any other material.
Do not activate electrical switches, telephone or any other
object that causes sparks if there is a smell of gas. Ventilate
the room by opening doors and windows and close the gas
central tap.
Do not place anything in the boiler.
Do not perform any cleaning operation if the appliance is not
disconnected from the main power supply.
Do not cover or reduce ventilation opening of the room where
the generator is installed.
Do not leave containers and infl ammable products in the in-
stallation room.
Do not attempt to repair the appliance in case of failure and/
or malfunctioning.
It is dangerous to pull or twist the electric cables.
Children or unskilled persons must not use the appliance.
Do not intervene on sealed elements.
C.A.I. models: do not cover or reduce the size of the ventila-
tion openings in the room where the boiler is installed. The
ventilation openings are vital for correct combustion.
For better use, remember that:
- a periodic external cleaning with soapy water not only improves
its aesthetic aspect but also preserves panelling from corrosion,
extending its life cycle;
- if the wall-mounted boiler is enclosed in pendant furniture, leave
at least 5 cm for ventilation and maintenance;