Operation And Maintenance Of Grease Separator Systems In Accordance With En 1825-2 And Din 4040 - Graf KLsepa.pop Manuel D'utilisation

Masquer les pouces Voir aussi pour KLsepa.pop:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5. Operation and Maintenance of Grease Separator Systems in Accordance
5.3.1. Measures to be carried out in connection with the disposal are
Complete draining and cleaning of the sludge trap and separator. For this the
layer of grease which has collected on the surface must first be extracted. This
prevents grease from entering the outlet as the water level falls during emptying
and being washed out of the separator once operation is restarted. Only once the
layer of grease has been completely removed may the water underneath be
pumped out.
Remove encrustations and deposits.
Clean the odour-proof cover and check the condition of the seal and sealing
effectiveness if necessary.
Clean the inlet and outlet pipes and the sampling system, if present, with warm
water (approx. 30°C). The water used for cleaning must then be pumped out
completely.
The entire system, sludge trap and grease separator must then be filled with
clean water in order to restore functionality for continued operation.
5.3.2. Volumes and coating thickness of the compact grease separator
NS
KLsepa.pop
[l/s]
1-200-2
2-200-2
1-200-3
2-200-3
1-400
2-400
2-500
4-500
4-700
7-700
10-1500
15-1500
Operating Manual for KLsepa.pop Grease Separator System
with EN 1825-2 and DIN 4040-100
Sludge trap
Volume
Fill level
max.
[l]
[cm]
1
200
40
2
1
200
41
2
1
400
62
2
2
500
73
4
4
700
41
7
10
1500
65
15
Grease collection area
Volume
50 %
[cm]
[l]
27
200
27
300
40
200
46
300
25
350
39
600
Container
Layer
Volume
thickness
max.
Total
[cm]
[l]
25
490
34
720
26
720
33
1000
20
2050
25
3150
23

Publicité

Chapitres

Table des Matières
loading

Table des Matières