G: Grille with straight blades, aluminium, blade pitch 25 mm (AL-E)
H: Grille with straight blades, aluminium, blade pitch 16.7 mm (AL-E)
Any combination is possible
B24, B230 – Open/Close actuators
Application
Open/Close actuators for the opening and closure of smoke control dampers, with automatic (AA) or manual release (MA).
With integral limit switches for capturing the end positions
Override control for up to 25 minutes
Ambient temperature for normal operation: –30 to 50 °C, up to 95% rh, no condensation (EN 60730-1)
Two integral limit switches with volt-free contacts can indicate the damper blade position (OPEN and CLOSED)
The connecting cables of the 24 V actuator are fitted with plugs, which ensure quick and easy connection to the TROX AS-i bus system
The connecting cable of the 230 V AC actuator is fitted with wire end ferrules
Variants
B24
24 V AC/DC supply voltage
BE24-12-ST TR: Torque 40 Nm
BLE24-ST TR: Torque 15 Nm
B230
Supply voltage 230 V AC
BE230-12 TR: Torque 40 Nm
BLE230 TR: Torque 15 Nm
The torque required to operate the smoke control damper depends on the size which is why the actuator type cannot be chosen freely.
Installation information
Feeding the electric connecting cable through the actuator encasing requires a drilled hole of the exact size (Ø max. + 1 mm)
A wire clamping bracket is required
For details on maintenance and inspection refer to the installation and operating manual
B24A – AS-EM/EK
Application
Module for the control of smoke control dampers
Capturing damper blade positions OPEN and CLOSED
Actuators can be started even without controller communication
LEDs for OPEN and CLOSED positions; monitoring of running time errors
Integral AS-Interface slave
Monitoring of signal reception
Master can be used to monitor the running time of the damper blade actuator
Supply voltage of the module and 24 V DC actuator using AS-Interface (2-wire control)
Plug-in connection for Belimo actuators (factory mounted and wired)
B24AS – AS-EM/SIL2
Application
Module for the control of smoke control dampers
Capturing damper blade positions OPEN and CLOSED
Approved up to SIL2 to IEC/EN 61508
Integral AS-Interface slave
Monitoring of signal reception
Master can be used to monitor the running time of the damper blade actuator
Connection with terminals
Supply voltage of the module and 24 V DC actuator using AS-Interface (2-wire control)
Plug-in connection for Belimo actuators (factory mounted and wired)
B24BKNE – Communication module