Trox Technik EK-JZ Mode D'emploi page 22

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Order example: EK-JZ-R/DE/800×1030×250/A0/B24A
Actuator encasing
Country of destination
Nominal size
Attachment 1
Attachment 2
Type
EK-JZ Smoke control damper
Actuator encasing as seen from the operating side
R
On the right (as standard)
Country of destination
DE
Germany
Other destination countries upon request
Nominal size [mm]
B × H × L
Attachments 1, Attachments 2, Dimensions and weight
F, A, B, C, D, E, G, H – Connecting subframes and cover grilles
Application
A connecting subframe (F) is required for sheet steel smoke extract ducts
Cover grilles are attached to the damper or to the end of ducts; this application has been approved based on a fire test to EN 1366-10
The cover grille free area is approx. 80% for crimped wire mesh (A) and approx. 70% for perforated metal plates
Cover grille variants C, D, E, G, H cover the blades of EK-JZ but not the actuator encasing
If you order a cover grille separately, you may choose a size that covers the damper blades and the actuator encasing and fix the grille along the perimeter of
the shaft wall
Connecting subframes and cover grilles are factory mounted to the dampers
Connecting subframes and cover grilles may also be ordered separately
Materials and surfaces
F: Connecting subframe made of galvanised sheet steel
Attachments 1
No entry: none
F0, 0F, FF
Connecting subframe, galvanised steel
Cover grille
A0, 0A, AA
Crimped wire mesh, 20 × 20, galvanised steel
B0, 0B, BB
Square perforated metal plate, 10 × 10, galvanised steel
C0, 0C, CC
Grille with slanted blades, aluminium
D0, 0D, DD
Grille with slanted blades, aluminium, additionally with crimped wire mesh, 20 × 20, galvanised steel
E0, 0E, EE
Grille with slanted blades, aluminium, additionally with welded wire mesh, 6 × 6, galvanised steel
The first character refers to the operating side, the second character refers to the installation side
e.g. FA: Connecting subframe on the operating side, crimped wire mesh on the installation side
Any combination is possible
Attachments 2
Belimo actuators
B24
BE 24-12; BLE 24-12, 24 V AC/DC
B230
BE 230-12; BLE 230-12, 230 V AC
Combinations of actuator and control module
B24A
BE 24-12 / BLE 24-12, with AS-EM/EK, 30 V DC (AS-i)
B24AS BE24-12 / BLE 24-12, with AS-EM/SIL2, 30 V DC (AS-i)
B24BKNE BE 24-12 / BLE 24-12, with BKNE230-24
B24C
BE 24-12 / BLE24-12, with BC24
B24D
BE 24-12 / BLE 24-12, with BRM-10-F-ST
B230D BE 230-12 / BLE 230-12, with BRM-10-F
Operating side, on th
Germany
800 × 1030 × 250
Cover grille on the opera
24 V AC/DC with TROXNETCOM con
 

Publicité