5
Electrical installation
Standard devices in the power range 15 ... 30 kW
Assignment of mains choke/mains filter
Installation to UL
Supply conditions
Range
Fuses
Cables
Observe all national and regional regulations!
9300
Type
Operation with mains choke/mains filter
EVS9327−xx
EVS9328−xx
EVS9329−xx
5.5.4
Assignment of mains choke/mains filter
9300
Mains choke
Type
EVS9327−xx
ELN3−0088H035−001
EVS9328−xx
ELN3−0075H045
EVS9329−xx
ELN3−0055H055
1)
RFI filter
2)
Footprint filter
162
Description
l
Only according to UL 248
l
Mains short−circuit current up to 5000 A
l
Mains short−circuit current up to 50000 A
l
Only in accordance with UL
l
The cable cross−sections specified in the following apply under the following conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C
Rated fuse current
Fuse
[A]
35
60
80
Interference voltage category according to EN 61800−3 and motor cable length
Component
c2
EZN3A0110H030
E82ZN22334B230
E82ZZ15334B230
EZN3A0080H042
E82ZN22334B230
EZN3A0055H060
E82ZN30334B230
l
: All classes permissible
rms
: Only classes "J", "T" or "R" permissible
rms
Cable cross−section
max. [m]
25
E82ZN22334B230
E82ZZ15334B230
EZN3B0110H030U
50
1)
50
25
E82ZN22334B230
50
EZN3B0080H042
25
E82ZN30334B230
50
EZN3B0055H060
L1, L2, L3, PE
[AWG]
8
4
4
Component
c1
max. [m]
10
1)
10
2)
50
10
50
10
50
EDKVS9332X DE/EN/FR 4.0