Transport and storage

3.4

Technical data

Control range
Fluid
Material
Seal
Body
Handwheel
Pipe
Valve insert spindle Stainless steel
4.
Transport and storage
Transport the product in its original packaging.
Store the product under the following conditions:
Temperature range
Relative air humidity
Particles
Mechanical influences
Radiation
Chemical influences
5.

Installation

Flush the pipework thoroughly before installing the
derivative temperature control set.
NOTICE
Damage to property due to lubricants
Seals can be destroyed by the use of grease
or oils.
f If necessary, flush dirt particles and
grease and oil residues out of the pipe-
work.
5.1
Installation of item no. 1341088 and
1341188
Procedure for: Derivative temperature control set
item no. 1341088 for Regudis W-HTU/TU or deriv-
ative temperature control set item no. 1341188 for
Regudis W-HTF
1. Close all ball valves.
2. Drain the dwelling station via the drain valve.
3. Unscrew (22 mm spanner) the blind plug from the
14
35 °C to 60 °C
EPDM, fibre materials
Brass, dezincification resistant
brass
Plastic
Copper (Cu-DHP-R200)
-20°C to +60°C
max. 95%
Store dry and free from
dust
Protected from mechani-
cal agitation
Protected from UV-rays
and direct sunlight
Do not store together
with solvents, chemicals,
acids, fuels or similar
substances
Derivative temperature control set
distributor (see Illust. 2).
4. Unscrew (12 mm spanner) the sealing plug from the
body (see Illust. 2).
Keep a cloth and a container at hand to collect
escaping water.
4
3
Illust. 2: Removal of the plugs Regudis W-HTU/TU
and Regudis W-HTF
(1)
Blind plug (22 mm spanner)
(2)
Drain valve
(3)
Body
(4)
Sealing plug (12 mm spanner)
5. Screw the adapter (see Illust. 1) into the body (see
Illust. 3).
6. Loosen the union nuts and the pipe clamps at the
body.
Illust. 3: Installation of the adapter Regudis W-HTU/
TU and Regudis W-HTF
(1)
Union nut (32 mm spanner)
(2)
Adapter (16 mm spanner)
7. Screw the valve into the distributor (see Illust. 4).
Pay attention to the orientation of the valve (the
white marking of the handhweel must point to the
front). Screw the body in until the sealing ring is
1