Electrical installation
Control terminals
Assignment of the plug connectors
Plug connector X6
Terminal
X6/+24
X6/GND
X6/DO1
X6/DI1
X6/DI2
X6/DI3
X6/DI4
X6/AI+
X6/AI−
X6/AG
X6/B+
X6/B−
X6/S24
X6/SO
X6/SI1
X6/SI2
Cable cross−sections and screw−tightening torques
Cable type
Flexible
We recommend to use control cables with a cable cross−section of 0.25 mm
116
Function
Low−voltage supply of the control
electronics
Reference potential of low−voltage supply
Digital output 1
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Analog input +
Analog input −
Reference potential of analog input
(internal ground)
Brake supply +
Brake supply −
Connection of "safe torque off" (formerly
"safe standstill")
Wire end ferrule
Cable cross−section
Without wire end
0.08 ... 1.5 mm
ferrule
(AWG 28 ... 16)
With insulated wire
0.25 ... 0.5 mm
end ferrule
(AWG 22 ... 20)
Electrical data
20 ... 30 V DC, 0. A (max. 1 A)
for starting current of 24 V:
max. 2 A for 50 ms
24 V DC, 0.7 A (max. 1.4 A)
short−circuit−proof
LOW:
−3 ... +5 V;
−3 ... +1.5 mA
HIGH:
+15 ... +30 V;
+2 ... +15 mA
Input current at 24 V DC:
8 mA per input
Adjustable with jumper strip X3:
−10 ... +10 V, max. 2 mA
−20 ... +20 mA
Resolution: 11 bits + sign
23 ... 30 V DC
max. 1.5 A
Set brake voltage so that the permissible
voltage at the brake is not under−run or
exceeded ˘ otherwise malfunction or
destruction!
^
120
Tightening torque
2
0.22 ... 0.25 Nm
(1.95 ... 2.2 lb−in)
2
l
Stripping length
5 mm for screw
connection
9 mm for spring
connection
2
.
EDKCSDX064 DE/EN/FR 3.0