2

Technical data

General data and operating conditions

2
Technical data
General data and operating conditions
Standards
Conformity
Protection
Type of protection
Insulation resistance
Leakage current
Ambient conditions
Temperature
Storage
Transport
Operation
Site altitude
Pollution
Vibration resistance
24
CE
Low−voltage Directive (2006/95/EC)
EN 60529
IP 20
NEMA 250
Protection against contact to
type 1
EN 61800−5−1
Overvoltage category III
> 2000 m: Overvoltage category II
EN 61800−5−1
> 3.5 mA
−25 ... +60 °C
−25 ... +70 °C
−10 ... +55 °C
Current derating from +40 to +55 °C: 2.5 %/°C
0 ... 4000 m amsl
1000 ... 4000 m amsl: Current derating by 5 %/1000 m
EN 61800−5−1
Pollution degree 2
EN 50178; IEC
Acceleration−resistant up to 0.7 g
61800−5−1;
Germanischer
Lloyd, general
conditions
l
Not in the wire range of
the terminals
Observe regulations
and safety instructions!
EDKLM3−XXX−002 DE/EN/FR 1.0