Setting The Baud Rate And Address - Lenze DeviceNet E82ZAFVC001 Instructions De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Setting the baud rate and address

Node address setting
)
Note!
The device address must be set via software, when the switches S7 and S8 are
in ON position.
In this case the switches S1 to S6 are ineffective.
ON
1
2
3
4
Fig. 2
Address assignment via DIP switch
)
Note!
If several controllers are connected to the network, the node addresses must
differ from each other.
The address (decimal number) is calculated by inserting the positions of switches S1 to S6
('0' = OFF and '1' = ON) into the following equation.
0
Address
= S6 · 2
dec
The equation can also be used to calculate the valency of a switch. The sum of valencies
results in the node address to be set:
Switch
S1
S2
S3
S4
S5
S6
EDK82ZAFVC001 DE/EN/FR 2.0
5
6
7
8
9
10
1
2
+ S5 · 2
+ S4 · 2
+ S3 · 2
Valency
32
16
8
4
2
1
l
Commissioning
Setting the baud rate and address
3
4
5
+ S2 · 2
+ S1 · 2
Example
Switch position
ON
ON
ON
OFF
OFF
OFF
ON
OFF
Node address
32 + 16+ 8 = 56