Forced Ventilated Or Naturally Ventilated Motors - Lenze ECSDS Série Instructions De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2.2.1

Forced ventilated or naturally ventilated motors

Parameter setting
The following codes can be set for I
Code
C0066
C0120
C0127
C0128
C0606
Calculate release time and I
Formula for release time
t + * ( t )
Formulae for I
L(t) +
If the controller is inhibited, the I
EDKCSDX064 DE/EN/FR 3.0
Forced ventilated or naturally ventilated motors
Meaning
2
Display of the I
x t load of the motor
Threshold: Triggering of error "OC6"
Threshold: Triggering of error "OC8"
Thermal motor time constant
Response to error "OC8"
2
x t load
z ) 1
ln 1 *
2
I Mot
I N
2
x t load
2
I
Mot
1 * e
100%
I
N
2
x t load is reduced:
t
*
L(t) + L
e
t
Start
l
Safety instructions
Thermal motor monitoring
2
x t monitoring:
Value range
0 ... 250 %
0 ... 120 %
0 ... 120 %
0.1 ... 50.0 min
TRIP, warning, off
Information
I
Actual motor current (C0054)
Mot
I
Rated motor current (C0088)
r
t
Thermal motor time constant
(C0128)
100
z
Threshold value in C0120 (OC6) or
C0127 (OC8)
Information
L(t)
Chronological sequence of the
2
I
x t load of the motor
(Display: C0066)
*t
I
Actual motor current (C0054)
Mot
t
Ir
Rated motor current (C0088)
t
Thermal motor time constant
(C0128)
2
L
I
x t load before controller inhibit
Start
If an error is triggered, the value
corresponds to the threshold
value set in C0120 (OC6) or C0127
(OC8).
2
Lenze setting
0 %
0 %
5.0 min
Warning
83