4.3
Fuses and cable cross−sections
Mains
3/PE AC
Operation with external mains choke/mains filter, installation according to
EN 60204−1
The data are recommendations. Other dimensioning/laying systems are possible (e.g.
according VDE 0298−4).
The cable cross−sections apply under the following conditions:
Use of PVC−insulated copper cables
ƒ
Conductor temperature < 70 °C, ambient temperature < 45°C
ƒ
No bundling of cables or cores
ƒ
Three loaded cores
ƒ
Type
E94AZMR0264xDB
E94ARNE0134
E94AZMR0474xDB
E94ARNE0244
Circuit breaker
Fuse of the utilisation category gG/gL or semiconductor fuses or the utilisation category gRL
1)
Universal−current−sensitive earth−leakage circuit breaker, RCD type B
If several devices or cable lengths > 50 m are used, it is possible that the circuit breaker will respond, depending on
the type of cable and the switching frequency.
Observe national and regional regulations!
Operation with external mains choke/mains filter, installation according to UL
Only use UL−approved cables, fuses and fuse holders.
UL fuse: Voltage 600 V; CC, J or T class fuses
Type
E94AZMR0264xDB
E94ARNE0134
E94AZMR0474xDB
E94ARNE0244
Fuse
1)
Universal−current−sensitive earth−leakage circuit breaker, RCD type B
If several devices or cable lengths > 50 m are used, it is possible that the circuit breaker will respond, depending on
the type of cable and the switching frequency.
Observe national and regional regulations!
EDK94ARN24 DE/EN/FR/ES/IT 3.0
Voltage
Voltage range
U
[V]
U
Lrated
230 ... 480
180 − 0 % ... 528 + 0 %
[A]
[A]
[mm
C32
−
−
80
standard installation
L1, L2, L3
[A]
[AWG]
45
6
70
3
l
Technical data
Fuses and cable cross−sections
Frequency range
[V]
Lrated
L1, L2, L3 − laying system
B2
C
2
2
]
[mm
]
[mm
10
6
25
16
motor group installation
L1, L2, L3
[A]
[AWG]
70
3
70
3
4
f [Hz]
45 ... 65
1)
FI
F
2
]
[mA]
-
−
-
−
1)
FI
[mA]
-
-
57