EDKCSCK002 .ðwV Montageanleitung Mounting Instructions Instructions de montage ECSCKxxx Kondensatormodul "Cold−Plate−Technik" Capacitor module in cold plate design Module condensateur en montage sur semelle de refroidissement...
Page 2
Lesen Sie zuerst diese Anleitung, bevor Sie mit den Arbeiten beginnen! Beachten Sie die enthaltenen Sicherheitshinweise. Please read these Instructions before you start working! Follow the enclosed safety instructions. Veuillez lire attentivement cette documentation avant toute action ! Les consignes de sécurité doivent impérativement être respectées.
Page 4
Lieferumfang Position Beschreibung Anzahl Kondensatormodul ECSCKxxx Beipack mit Befestigungsmaterial Montageanleitung Bohrschablone Hinweis! Die Steckverbinder ECSZK000X0B müssen gesondert bezogen werden. Anschlüsse und Schnittstellen Position Beschreibung ausführliche Informationen Anschlüsse Zwischenkreisspannung Steueranschluss Überbrückung der Ladestrombegrenzung EDKCSCK002 DE/EN/FR 1.1...
Page 5
Diese Anleitung ist gültig für Kondensatormodule ECSCKxxx ab dem Gerätestand: Gerätetyp Bauform E = Einbaugerät IP20 D = Durchstoßtechnik (thermische Sepa- rierung) C = Cold−Plate−Technik Kapazität 001 = 705 mF (±20 %) 002 = 1410 mF (±20 %) Spannungsklasse 4 = 400 V/480 V Technische Ausführung B = Standard Variante...
Lenze−Kondensatormodule (gemäß Niederspannungsrichtlinie 73/23/EWG) Allgemein Lenze−Kondensatormodule können während des Betriebs − ihrer Schutzart ent- sprechend − spannungsführende Teile haben. Oberflächen können heiß sein. Bei unzulässigem Entfernen der erforderlichen Abdeckung, bei unsachgemäßem Einsatz, bei falscher Installation oder Bedienung besteht die Gefahr von schweren Personen−...
Page 9
Sicherheitshinweise Allgemeine Sicherheits− und Anwendungshinweise Bestimmungsgemäße Verwendung Kondensatormodule sind Komponenten, die zum Einbau in elektrische Anlagen oder Maschinen bestimmt sind. Sie sind keine Haushaltsgeräte, sondern als Kom- ponenten ausschließlich für die Verwendung zur gewerblichen Nutzung bzw. pro- fessionellen Nutzung im Sinne der EN 61000−3−2 bestimmt. Die Dokumentation enthält Hinweise zur Einhaltung der Grenzwerte nach EN 61000−3−2.
Page 10
Sicherheitshinweise Allgemeine Sicherheits− und Anwendungshinweise Elektrischer Anschluss Beachten Sie bei Arbeiten an unter Spannung stehenden Kondensatormodulen die geltenden nationalen Unfallverhütungsvorschriften (z. B. VBG 4). Führen Sie die elektrische Installation nach den einschlägigen Vorschriften durch (z. B. Leitungsquerschnitte, Absicherungen, Schutzleiteranbindung). Zusätzliche Hinweise enthält die Dokumentation.
Sicherheitshinweise Restgefahren Restgefahren Personenschutz Überprüfen Sie vor Arbeiten am Kondensatormodul, ob alle ƒ Leistungsklemmen spannungslos sind, denn – nach dem Abschalten der Netzspannung am Versorgungsmodul führen die Leistungsklemmen +UG und −UG noch mindestens 3 Minuten gefährliche Spannung. – bei gestopptem Motor führen die Leistungsklemmen +UG und −UG gefährliche Spannung.
Sicherheitshinweise Sicherheitshinweise für die Installation nach UL oder UR Sicherheitshinweise für die Installation nach U oder U Warnings! General markings: Use 60/75 °C or 75 °C copper wire only. ƒ Maximum ambient temperature 55 °C, with reduced output current. ƒ Terminal tightening torque of lb−in (Nm) X 23 ƒ...
Sicherheitshinweise Definition der verwendeten Hinweise Definition der verwendeten Hinweise Um auf Gefahren und wichtige Informationen hinzuweisen, werden in dieser Do- kumentation folgende Signalwörter und Symbole verwendet: Sicherheitshinweise Aufbau der Sicherheitshinweise: Gefahr! (kennzeichnet die Art und die Schwere der Gefahr) Hinweistext (beschreibt die Gefahr und gibt Hinweise, wie sie vermieden werden kann) Piktogramm und Signalwort...
Page 14
Sicherheitshinweise Definition der verwendeten Hinweise Spezielle Sicherheitshinweise und Anwendungshinweise für UL und UR Piktogramm und Signalwort Bedeutung Sicherheitshinweis oder Anwendungshinweis für den Betrieb eines UL−approbierten Geräts in UL−approbierten Anlagen. Warnings! Möglicherweise wird das Antriebssystem nicht UL−ge- recht betrieben, wenn nicht die entsprechenden Maß- nahmen getroffen werden.
Technische Daten Bemessungsdaten Allgemeine elektrische Daten Einhaltung der Anforderungen nach EN 61800−3 Störaussendung Einhaltung der Grenzwertklasse A nach EN 55011 (erreicht mit anwendungstypischem Summenfilter) Störfestigkeit Anforderungen nach EN 61800−3 Anforderung Norm Schärfegrade EN 61000−4−2 3, d. h. 8 kV bei Luftentladung 6 kV bei Kontaktentla- dung leitungsgeführte Hochfre-...
Mechanische Installation Wichtige Hinweise Mechanische Installation Wichtige Hinweise Kondensatormodule der Reihe ECS verfügen über die Schutzart IP20 und sind ƒ daher nur für den Einbau in Schaltschränken bestimmt. Bei verunreinigter Kühlluft (Staub, Flusen, Fette, aggressive Gase): ƒ – Ausreichende Gegenmaßnahmen treffen, z. B. separate Luftführung, Einbau von Filtern, regelmäßige Reinigung.
Mechanische Installation Montage in Cold−Plate−Technik Montage in Cold−Plate−Technik Die Kondensatormodule Typ ECSCKxxx sind für die Montage in Cold−Plate−Technik (z. B. auf Summenkühlern) bestimmt. Anforderungen an den Summenkühler Für den sicheren Betrieb der Kondensatormodule sind folgende Bedingungen ein- zuhalten: Die Kontaktfläche zwischen Summenkühler und Kondensatormodul muss ƒ...
Mechanische Installation Montage in Cold−Plate−Technik Montageschritte 3.2.2 Montageschritte À Á Â ECSXK030 Abb. 3−2 Montage bei Bauform "Cold−Plate−Technik" So montieren Sie das Kondensatormodul: 1. Befestigungsbohrungen auf Montagefläche vorbereiten. – Dazu Bohrschablone anlegen. 2. Kontaktfläche von Summenkühler und Kühlplatte des Kondensatormoduls säubern und entfetten (z.
Elektrische Installation EMV−gerechte Verdrahtung (Aufbau des CE−typischen Antriebssystems) Elektrische Installation EMV−gerechte Verdrahtung (Aufbau des CE−typischen Antriebssystems) Allgemeine Hinweise Die elektromagnetische Verträglichkeit einer Maschine ist abhängig von der ƒ Art und Sorgfalt der Installation. Beachten Sie besonders: – Aufbau – Filterung –...
Page 22
Elektrische Installation EMV−gerechte Verdrahtung (Aufbau des CE−typischen Antriebssystems) Aufbau Versorgungsmodule, Kondensatormodule (optional), Achsmodule, ƒ Funk−Entstörfilter und Netzdrossel großflächig mit geerdeter Montageplatte verbinden: – Montageplatten mit elektrisch leitender Oberfläche (verzinkt oder rostfreier Stahl) erlauben eine dauerhafte Verbindung. – Lackierte Platten sind nicht geeignet für die EMV−gerechte Installation. Verwendung des Kondensatormoduls ECSxK...: ƒ...
Page 23
Elektrische Installation EMV−gerechte Verdrahtung (Aufbau des CE−typischen Antriebssystems) Schirmung Am Achsmodul den Schirm der Motorleitung ƒ – mit dem Schirmbefestigungs−Set ECSZS000X0B001 auflegen. – großflächig mit der Montageplatte unterhalb des Achsmoduls verbinden. – Empfehlung: Schirm mit Erdungsschellen auf metallisch blanken Montageflächen ausführen. Bei Schützen, Motorschutzschalter oder Klemmen in der Motorleitung: ƒ...
Elektrische Installation Leistungsanschlüsse Leistungsanschlüsse Stop! Das Kondensatormodul ist ausschließlich für den Betrieb an ƒ symmetrischen Netzen zugelassen. Ein Betrieb an Außenleiter−geerdeten Netzen ist nicht zulässig. Beachten Sie die maximal zulässige Netzspannung. Eine höhere ƒ Spannung zerstört das Kondensatormodul. Der Ableitstrom gegen Erde (PE) ist > 3.5 mA AC bzw. > 10 mA DC. ƒ...
Page 25
Elektrische Installation Leistungsanschlüsse Geschirmte Leitungen Folgende Faktoren bestimmen maßgeblich die Wirkung der geschirmten Leitun- gen: Gute Schirmanbindung ƒ – Schirm großflächig auflegen Niedriger Schirmwiderstand ƒ – Nur Schirme mit verzinntem oder vernickeltem Kupfergeflecht verwenden (Schirme aus Stahlgeflecht sind ungeeignet). Hoher Überdeckungsgrad des Schirmgeflechts ƒ...
Eine Absicherung der Zwischenkreisversorgung ist bei Verwendung ƒ netzseitig abgesicherter Versorgungsmodule der Reihe ECS nicht erforderlich. Bei Verwendung von Lenze−Geräten der Reihen 82xx und 93xx im ƒ Zwischenkreisverbund mit einem DC−Dauerstrom > 40 A setzen Sie folgende Sicherungen ein: Schmelzsicherung...
Elektrische Installation Steueranschluss X26 Steueranschluss X26 Klemmenbelegung Klemme Funktion Elektrische Daten Anschluss zur Überbrückung der Ladestrombe- 21,8 ... 30 V DC, grenzung max. 1,5 A Die Ladestrombegrenzung wird überbrückt, wenn X26 = HIGH (24 V DC). ƒ Die Polarität hat keinen Einfluss auf die Funktion der Ladestrombegrenzung. ƒ...
Elektrische Installation Verdrahtung Betrieb mit Versorgungsmodul ECSxE Verdrahtung Installieren Sie das Kondensatormodul zwischen dem Versorgungsmodul und dem/den Achsmodul(en). Ist die Gesamtleitungslänge im Zwischenkreisverbund > 5 m, installieren Sie das Kondensatormodul möglichst nah am Achsmodul mit der größten Leistung. 4.4.1 Betrieb mit Versorgungsmodul ECSxE Stop! Die Ladestrombegrenzung (X26) des Kondensatormoduls dauerhaft ƒ...
Page 29
Elektrische Installation Verdrahtung Betrieb mit Versorgungsmodul ECSxE F1...F3 ECSxE... ECSxK... ECSxS/P/M/A... B1 B2 U V W 24 V DC ECSXX004 Abb. 4−2 Verdrahtung Kondensatormodul ECSxK... HF−Schirmabschluss durch großflächige PE−Anbindung verdrillte Leitungen Netzschütz F1 ... F4 Absicherung Netzdrossel / Netzfilter, optional Hilfsschütz Systemleitung ˘...
Elektrische Installation Verdrahtung Betrieb mit anderem Versorger 4.4.2 Betrieb mit anderem Versorger Stop! Frühestens 1 Sekunde nach dem Netzeinschalten darf die ƒ Ladestrombegrenzung überbrückt werden (X26 = HIGH). Antriebsregler erst freigeben (X6/SI1 = HIGH), wenn die ƒ Ladestrombegrenzung überbrückt ist. HIGH (1) ü...
Installation prüfen Installation überprüfen Überprüfen Sie nach Abschluss der Installation ... die Verdrahtung auf Vollständigkeit, Kurzschluss und Erdschluss. ƒ den Leistungsanschluss (X23): ƒ – Polung der Einspeisung der Zwischenkreisspannung über Klemmen +UG, −UG den Steueranschluss (X26): ƒ – Überbrückung der Ladestrombegrenzung je nach angeschlossenem Versorgungsmodul.
Page 32
Scope of supply Position Description Number Capacitor module ECSCKxxx Accessory kit with fixing material Mounting instructions Drilling jig Note! The ECSZK000X0B connectors must be ordered separately. Connections and interfaces Position Description Detailed information Connections DC−bus voltage Control connection Bridging of the charging current limitation EDKCSCK002 DE/EN/FR 1.1...
Page 33
These Operating Instructions are valid for ECSCKxxx capacitors modules as of version: Type Design E = Built−in unit IP20 D = Push−through technique (thermal separation) C = Cold−plate technique Capacity 001 = 705 mF (±20 %) 002 = 1410 mF (±20 %) Voltage class 4 = 400 V/480 V Technical version...
General safety and application information for Lenze capacitor modules (according to Low−Voltage Directive 73/23/EWG) General During operation, Lenze capacitor modules can include live parts, depending on their type of protection. Surfaces can be hot. If the required cover is removed or the modules are used inappropriately or instal- led or operated incorrectly, severe damage to persons or material can occur.
Page 37
Safety instructions General safety and application information Transport, storage The notes on transport, storage and appropriate handling must be observed. Observe the climatic conditions required to EN 50178. Installation The capacitor modules must be installed and cooled according to the regulations given in the corresponding Instructions.
Page 38
Safety instructions General safety and application information Maintenance and servicing The capacitor modules are free of maintenance if the prescribed conditions of ope- ration are observed. In operating areas with polluted ambient air, the cooling surfaces of the capacitor module can get dirty or the cooling openings can block. Under these conditions a regular cleaning of the cooling surfaces and cooling openings is essential.
Safety instructions Residual hazards Residual hazards Protection of persons Before working on the capacitor module, check that no voltage is applied to ƒ the power terminals, – because the power terminals +UG and −UG at the supply module remain live for at least 3 minutes after mains switch−off. –...
Safety instructions Safety instructions for the installation according to UL or UR Safety instructions for the installation according to U or U Warnings! General markings: Use 60/75 °C or 75 °C copper wire only. ƒ Maximum ambient temperature 55 °C, with reduced output ƒ...
Safety instructions Definition of notes used Definition of notes used The following signal words and symbols are used in this documentation to indicate dangers and important information: Safety instructions Structure of safety instructions: Danger! (characterises the type and severity of danger) Note (describes the danger and gives information about how to prevent dangerous situations)
Page 42
Safety instructions Definition of notes used Special safety instructions and application notes for UL and UR Pictograph and signal word Meaning Safety or application note for the operation of a UL−approved device in UL−approved systems. Warnings! Possibly the drive system is not operated in compliance with UL if the corresponding measures are not taken.
Technical data General data/operating conditions Technical data General data/operating conditions Standards and operating conditions Conformity Low−Voltage Directive (73/23/EWG) Approvals UL 508C Power Conversion Equipment Underwriter Laboratories (file no. E132659) for USA and Canada Vibration resistance Accelerational stability up to 0.7 g (Germanischer Lloyd, general conditions) Climatic conditions Class 3K3 to EN 50178 (without condensation, relative humidity...
Technical data Rated data General electrical data Compliance with EN 61800−3 Noise emission Compliance with limit value class A to EN 55011 (achieved with application−specific collective filter) Noise immunity Requirements to EN 61800−3 Requirements Standard Severity EN 61000−4−2 3, i. e. 8 kV with air discharge 6 kV with contact discharge...
Mechanical installation Important notes Mechanical installation Important notes Capacitor modules of series ECS feature enclosure IP20 and, for this reason, ƒ are intended for installation in control cabinets. If the cooling air contains air pollutants (dust, fluff, grease, aggressive gases): ƒ...
Mechanical installation Mounting in cold plate technique Mounting in cold plate technique The capacitor modules of type ECSCKxxx are intended for mounting in cold−plate technique (e.g. on collective coolers). Requirements for collective coolers The following requirements must be met to ensure a safe operation of the capaci- tor modules: The contact surface between collective cooler and capacitor module must be ƒ...
Mechanical installation Mounting in cold plate technique Assembly steps 3.2.2 Assembly steps À Á Â ECSXK030 Fig.8−2 Mounting for "cold−plate technique" design How to mount the capacitor module: 1. Prepare the fixing holes on the mounting plate. – Apply a drilling jig for this purpose. 2.
Electrical installation Wiring according to EMC (installation of a CE−typical drive system) Electrical installation Wiring according to EMC (installation of a CE−typical drive system) General notes The electromagnetic compatibility of a machine depends on the type of ƒ installation and care taken. Especially consider the following: –...
Page 50
Electrical installation Wiring according to EMC (installation of a CE−typical drive system) Assembly Connect power supply modules, capacitor modules (optional), axis modules, ƒ RFI filters and mains choke with earthed mounting plate with a surface as large as possible – Mounting plates with conductive surfaces (zinc−coated or stainless steel) allow permanent contact.
Page 51
Electrical installation Wiring according to EMC (installation of a CE−typical drive system) Shielding Connect the motor cable shield to the axis module ƒ – with the shield mounting kit ECSZS000X0B001. – to the mounting plate below the axis module with a large surface. –...
Electrical installation Power connections Power connections Stop! The capacitor module is approved exclusively for operation at ƒ symmetrical mains. An operation at external conductor−earthed mains is not permissible. Observe the maximum permissible mains voltage. A higher voltage ƒ destroys the capacitor module. The discharge current to earth (PE) is >...
Page 53
Electrical installation Power connections Shielded cables Observe the following to increase the effect of shielded cables: Good shield connection ƒ – Ensure a contact surface as large as possible Low shield resistance ƒ – Only use shields with tin−plated or nickel−plated copper braids (shields with steel braids cannot be used).
When ECS series supply modules with a mains−side protection are used, the ƒ DC−bus supply does not need to be fused. When Lenze devices of the 82xx and 93xx series are used in DC−bus ƒ connections with a continuous DC current > 40 A, install the following fuses:...
Electrical installation Control connection X26 Control connection X26 Terminal assignment Terminal Function Electrical data Connection for bridging the charging current 21.8 ... 30 V DC, limitation max. 1.5 A The charging current limitation is bridged if X26 = HIGH (24 V DC). ƒ...
Electrical installation Wiring Operation with ECSxE power supply module Wiring Install the capacitor module between the power supply module and the axis mo- dule(s). If the total cable length in the DC−bus connection is longer than 5 m, install the ca- pacitor module as close as possible to the axis module with the highest power.
Page 57
Electrical installation Wiring Operation with ECSxE power supply module F1...F3 ECSxE... ECSxK... ECSxS/P/M/A... B1 B2 U V W 24 V DC ECSXX004 Fig.9−2 Wiring of capacitor module ECSxK... HF shield termination by large−surface PE connection Twisted cables Mains contactor F1 ... F4 Fusing Mains choke/mains filter, optional Contactor relay...
Electrical installation Wiring Operation with another supplier 4.4.2 Operation with another supplier Stop! After mains connection, wait at least one second before bridging ƒ the charging current limitation (X26 = HIGH). Only release the controller (X6/SI1 = HIGH) if the charging current ƒ...
Installation check Installation check After completing the installation, check ... The wiring for completeness, short circuit and earth fault. ƒ The power connection (X23): ƒ – Polarity of the DC−bus voltage supply via terminals +UG, −UG The control connection (X26): ƒ...
Equipement livré Position Description Nombre Module condensateur ECSCKxxx Matériel de fixation Instructions de montage Gabarit Remarque importante ! Les connecteurs à fiches ECSZK000X0B doivent être achetés séparément. Raccordements et interfaces Position Description Informations détaillées Raccordements Tension du bus CC Raccordement de commande Shuntage du régulateur du courant de charge EDKCSCK002 DE/EN/FR 1.1...
Page 61
Le présent document s’applique aux modules condensateurs ECSCKxxx à partir de la version suivante : Type d’appareil Forme de construction E = montage sur panneau IP20 D = montage traversant (séparation thermique) C = montage sur semelle de refroidissement Capacité 001 = 705 mF (±20 %) 002 = 1410 mF (±20 %) Classe de tension...
Instructions générales de sécurité et d’utilisation (conformes à la directive Basse Tension 73/23/CEE) Généralités Selon leur degré de protection, les modules condensateurs Lenze peuvent avoir, pendant leur fonctionnement, des parties accessibles sous tension. Les surfaces peuvent aussi être brûlantes. La suppression non autorisée de la protection prescrite, un usage non conforme à...
Page 65
Consignes de sécurité Instructions générales de sécurité et d’utilisation Utilisation conforme à l’application Les modules condensateurs sont des composants destinés à être incorporés dans des installations ou machines électriques. Ils ne constituent pas des appareils do- mestiques, mais des éléments à usage industriel et professionnel au sens de la norme EN 61000−3−2.
Page 66
Consignes de sécurité Instructions générales de sécurité et d’utilisation Raccordement électrique Lorsque des travaux sont effectués sur le module condensateur sous tension, les prescriptions nationales en vigueur pour la prévention d’accidents doivent être re- spectées (par exemple VBG 4). L’installation électrique doit être exécutée en conformité avec les prescriptions proposées (par exemple sections des conducteurs, protection par coupe−circuit à...
Page 67
Consignes de sécurité Instructions générales de sécurité et d’utilisation Traitement des déchets Les métaux et les matières plastiques sont recyclables. Les cartes électroniques sont à évacuer selon un traitement spécifique. Tenir impérativement compte des instructions de sécurité et d’utilisation des produits contenues dans ce document ! EDKCSCK002 DE/EN/FR 1.1...
Consignes de sécurité Dangers résiduels Dangers résiduels Protection des personnes Avant de procéder aux travaux sur le module condensateur, vérifier si toutes ƒ les bornes de puissance sont hors tension. En effet, – les bornes de puissance +UG et −UG sont encore sous tension pendant 3 min au minimum après coupure réseau du module d’alimentation ;...
Consignes de sécurité Consignes de sécurité pour l’installation selon UL ou UR Consignes de sécurité pour l’installation selon U ou U Warnings! General markings: Use 60/75 °C or 75 °C copper wire only. ƒ Maximum ambient temperature 55 °C, with reduced output ƒ...
Consignes de sécurité Définition des conventions utilisées Définition des conventions utilisées Pour indiquer des risques et des informations importantes, la présente documen- tation utilise les mots et symboles suivants : Consignes de sécurité Présentation des consignes de sécurité Danger ! (Le pictogramme indique le type de risque.) Explication (L’explication décrit le risque et les moyens de l’éviter.)
Page 71
Consignes de sécurité Définition des conventions utilisées Consignes de sécurité et d’utilisation spécifiques selon UL et UR Pictogramme et mot associé Signification Consigne de sécurité ou d’utilisation pour le fonctionnement d’un appareil homologué UL dans des installations homologuées UL Warnings! Le système d’entraînement risque de ne pas être utilisé...
Spécifications techniques Caractéristiques générales/conditions d’utilisation Spécifications techniques Caractéristiques générales/conditions d’utilisation Normes et conditions d’utilisation Conformité Directive Basse Tension (73/23/CEE) Homologations UL 508C Power Conversion Equipment Underwriter Laboratories (File No. E132659) pour les Etats−Unis et le Canada Résistance aux chocs Résistance à l’accélération jusqu’à 0,7 g (Germanischer Lloyd, conditions générales) Conditions climatiques Classe 3K3 selon EN 50178 (sans condensation, humidité...
Spécifications techniques Caractéristiques nominales Caractéristiques électriques générales Respect des exigences selon EN 61800−3 Perturbations radioélectriques : émission Respect des valeurs limites classe A selon EN 55011 (par la mise en place d’un filtre commun adapté) Protection contre les parasites Exigences selon EN 61800−3 Exigence Norme Degré...
Installation mécanique Remarques importantes Installation mécanique Remarques importantes Les modules condensateurs de la série ECS disposant de l’indice de ƒ protection IP20, ils sont uniquement destinés à un montage dans l’armoire électrique. Lorsque l’air de refroidissement contient des impuretés (poussières, ƒ...
Installation mécanique Montage sur semelle de refroidissement Montage sur semelle de refroidissement Les modules condensateurs de type ECSCKxxx sont conçus pour un montage sur semelle de refroidissement (sur des radiateurs communs, par exemple). Caractéristiques requises du radiateur commun Pour assurer un fonctionnement sécurisé des modules condensateurs, respecter les conditions suivantes.
Installation mécanique Montage sur semelle de refroidissement Encombrements 3.2.1 Encombrements Remarque importante ! Avec kit de fixation de blindage ECSZS000X0B001 : espace de montage sous le module > 195 mm ƒ ECSXK009 Fig.13−1 Encombrements pour forme de construction "montage sur semelle de refroidissement" Module condensateur Encombrements [mm] Type...
Installation mécanique Montage sur semelle de refroidissement Opérations de montage 3.2.2 Opérations de montage À Á Â ECSXK030 Fig.13−2 Montage pour forme de construction "montage sur semelle de refroidissement" Pour le montage du module condensateur, procéder comme suit : 1. Préparer les trous de fixation sur la surface de montage. –...
Installation électrique Câblage conforme CEM (installation d’un système d’entraînement de type CE) Installation électrique Câblage conforme CEM (installation d’un système d’entraînement de type CE) Généralités La compatibilité électromagnétique d’une machine dépend de la manière de ƒ câbler et du soin apporté à l’installation. Tenir compte, en particulier, –...
Page 79
Installation électrique Câblage conforme CEM (installation d’un système d’entraînement de type CE) Montage Pour les modules d’alimentation, les modules condensateurs (en option), les ƒ modules d’axe, les filtres antiparasites RFI et les selfs réseau, il est nécessaire d’appliquer une surface de contact importante sur la plaque de montage reliée à...
Page 80
Installation électrique Câblage conforme CEM (installation d’un système d’entraînement de type CE) Blindage Sur le module d’axe, raccorder le blindage du câble moteur ƒ – avec le kit de fixation de blindage ECSZS000X0B001 – et le relier avec la plaque de montage par une surface importante en dessous du module d’axe.
Installation électrique Partie puissance Partie puissance Stop ! Le module condensateur est uniquement conçu pour fonctionner ƒ sur des réseaux symétriques. Le fonctionnement sur des réseaux mis à la terre par conducteur extérieur est interdit. Respecter la tension réseau maximale autorisée. Une tension plus ƒ...
Page 82
Installation électrique Partie puissance Câbles blindés L’efficacité des câbles blindés est conditionnée par les facteurs suivants : raccordement correct du blindage ƒ – Appliquer le blindage par une surface de contact importante. faible résistance au blindage ƒ – Utiliser uniquement des tresses de cuivre étamées ou nickelées (les tresses en acier ne conviennent pas).
CC n’est pas nécessaire. En cas d’utilisation d’appareils Lenze séries 82xx et 93xx en bus CC avec un ƒ courant CC permanent > 40 A, prévoir les fusibles suivants :...
Installation électrique Raccordement de commande X26 Raccordement de commande X26 Affectation des bornes Borne Fonction Caractéristiques électriques Raccordement du shuntage du régulateur du 21,8 ... 30 V CC, courant de charge 1,5 A maxi Le régulateur du courant de charge est shunté lorsque X26 = HAUT (24 V CC). ƒ...
Installation électrique Câblage Fonctionnement avec un module d’alimentation ECSxE Câblage Installer le module condensateur entre le module d’alimentation et le ou les mo- dule(s) d’axe. Si la longueur totale du câble au niveau du bus CC est > 5 m, installer le module con- densateur le plus près possible du module d’axe le plus puissant.
Page 86
Installation électrique Câblage Fonctionnement avec un module d’alimentation ECSxE F1...F3 ECSxE... ECSxK... ECSxS/P/M/A... B1 B2 U V W 24 V DC ECSXX004 Fig.14−2 Câblage du module condensateur ECSxK... Blindage HF via surface de contact importante avec la terre (PE) Câbles torsadés Contacteur réseau F1 ...
Installation électrique Câblage Fonctionnement avec un autre module d’alimentation 4.4.2 Fonctionnement avec un autre module d’alimentation Stop ! Le shuntage du régulateur du courant de charge ne peut avoir lieu ƒ qu’au bout d’1 seconde au moins après la mise sous tension (X26 = HAUT).
Vérification de l’installation Vérification de l’installation Une fois l’installation terminée, vérifier ... le câblage dans son intégralité pour éviter un court−circuit ou un défaut de ƒ mise à la terre, le raccordement de puissance (X23) : ƒ – polarité de l’alimentation de la tension du bus CC via bornes +UG, −UG, le raccordement de commande (X26) : ƒ...
Page 89
Vérification de l’installation EDKCSCK002 DE/EN/FR 1.1...