6
Operation
6.1
When you receive the Miniflow it contains a converter preset in the factory. The factory default settings
can be changed on site. For more information, refer to Section 6.2 and 6.3. The following table provides
an overview of the default settings:
Factory default settings
6.2
Open the cover and use the DIP switches to set the equipment. The following table contains the switch
positions for setting damping, unit, current output and pulse output for Miniflow without a display. Care-
fully close the housing once the converter has been set. Ensure that the cover seal is in the correct posi-
tion as this is the only way of ensuring the IP 65 type of protection.
The factory default setting for all switches is "On"
Fig. 12:
Brief overview of function of DIP switch
The S6 switch should always be set to "On".
GB 16
FXL5000 (Miniflow)
Overview of factory default settings for converter
Measurement range
DN 10
DN 15
DN 25
DN 50
Unit
Current output (option)
Damping
Pulse output
Setting Miniflow in version without display
Version without display
DIP switch
8
Pulse output/contact output (inlet/
outlet signalling)
7
0 - 20 / 4 - 20 mA
6
Operation
5
Damping
4
Unit (litre/US gallons)
3
Measurement range
2
Measurement range
1
Measurement range
ON
OFF
50 l/min
100 l/min
300 l/min
1200 l/min
l/min
4 - 20 mA
5 sec.
1 pulse / litre
6 Operation
DIP switch