For Natural Gas :
Input (MBH)
=
Example: Natural Gas - Gas flow from
Meter = 2 cu ft
Measured time = 72 seconds
=
For Propane (LP):
Input (MBH)
=
Input Rate (MBH)
For Metric formulas- See Glossary
2.
Compare measured input to table below. If calculated input is not in range given in Table 9-2, check firing rate again after
setting the combustion following steps in section 9.10.
9.13 Parameter Settings
Program boiler electronic board parameters as follows:
• Press
and
the set value;
• Press
or
• Press
, value of selected parameter begins flashing, press
• Press
to confirm the value or press
Further information in regards to parameters listed in the following table are supplied together with required accessories if
necessary.
9.14 Description Of Parameters: Factory Settings
P01
Manufacturer information
Gas used
P02
00 = Gas A (Natural Gas)
01 = Gas E (LPG Gas)
Hydraulic system
00 = instantaneous appliance
03 = instantaneous appliance with pre-heat function
04 = heating only appliance with DHW thermostat
P03
05 = appliance with external storage indirect tank
08 = heating only appliance
13 = instantaneous appliance with pre-heat function for solar application
Programmable relay 1 setting (optional):
00 = no function is associated
01 = close contact with a room thermostat request (other than a BAXI thermostat)
02 = close contact with a BAXI room thermostat request
03 = relay for indicating low water pressure
04 = relay for error code display
05 = relay for kitchen fan function
07 = relay for post circulation pump
09 = DHW relay on with DHW program setting
P04
10 = DHW relay on with DHW request; if P64 = 1 relay on with CH and DHW request
13 = relay for Cooling function
14 = close contact with room thermostat request (120V~) with post circulation
15 = close contact with open therm remote control request with post circulation
Programmable relay 2 setting (optional):
P05
(Same configurations as Relay 1-P04)
240012485 REV A [12/30/2018]
3600 x
cu ft
seconds
3600 x 2 cu ft
= 100 MBH
72 seconds
9160 x
cu ft
seconds
together, hold them down for 6 seconds until program "P01" appears on the display alternated with
to scroll the list of parameters;
to exit without saving.
parameters continued on
Table 9-2 Input Rate @ High Fire (MBH)
to change the value;
next page
46
Approximate Rate @ 100%
Fire (MBH)
Size
1.48 GA
164
60 GA
205
FACTORY SETTINGS
1.48 GA
01
00
08
02
04
60 GA
00