2.
Once having entered the Floating Suction Pressure menu, the plug-in is confi gured in several steps, starting
from the last tab on the right, to the fi rst on the left.
2.1 Rack selection
In the "Racks" tab, choose which racks to enable for the Floating suction function.
Confi guration procedure:
1.
tick the checkbox relating to the desired devices;
2.
click "Save" in the top-right corner.
The confi guration procedure is illustrated in Figure 2.a.
2.2 Rack association
If there is at least one rack selected for the Floating suction function, a number of units can then be associated
with the rack. Each rack can have more than one unit associated ; each unit however can only be associated
with one rack.
In the "Association" tab, proceed as follows
1.
double click on a compressor rack, its name will be shown in the "Selected Rack" text box;
2.
select the devices from the list on the left;
3.
tick the "Smooth line control" checkbox only if all the devices feature this function;
4.
click on the RIGHT arrow to associate the units with the rack;
5.
click "Save" in the top-right corner.
FS CONFIGURATION ON PVPRO
Fig. 2.a
9
ENG
STEP 2
STEP 1