10. Detailed settings
3. Select "TAG short" and confirm with [↵].
4. Change figure using [▲] [▼] and confirm with [↵]. The cursor
EN
moves to the next figure. Repeat for each figure.
» TAG short is set.

10.2.2 Setting the TAG long

TAG long enables 32 figures with alphanumeric characters (all characters in accordance
®
with HART
revision 7). TAG long can be displayed in the additional display.
Setting is made as described in chapter 10.2.1 "TAG short".

10.3 Setting the alarm signal

Alarm signal downscale (3.5 mA)
In the event of a failure in the process transmitter, the output signal changes itself to
3.5 mA.
Alarm signal upscale (21.5 mA)
In the event of a failure in the process transmitter, the output signal changes itself to
21.5 mA.
1. Open the operating menu with [↵].
Select "Detail setup" and confirm with [↵].
2. Select "Current out" and confirm with [↵].
3. Select "Alarm signal" and confirm with [↵].
4. Select alarm signal and confirm with [↵].
3.5 mA = alarm signal downscale
21.5 mA = alarm signal upscale
» Alarm signal is set.
46
WIKA operating instructions, model DMSU21A