9. Diagnostic functions

9.2 Performing a current simulation

The selected or entered current value will be simulated and output as the PV (primary
value).
1. Open the operating menu with [↵].
Select "Diagnostic" and confirm with [↵].
2. Select "Simulation" and confirm with [↵].
3. Select "Current sim." and confirm with [↵].
4. Select the current value or define via "Input".
Change digit using [▲] [▼] and confirm with [↵]. The cursor
moves to the next digit. Repeat for each digit.
» Simulation is active.
5. Ending the simulation. Press [ESC] to do this.

9.3 Displaying/resetting drag pointer

The drag pointer function indicates the limit values reached since the last reset. These
limit values can be displayed and reset.

9.4 Drag pointer P

Displays the minimum and maximum pressure that has occurred since the last reset.
Displaying
1. Open the operating menu with [↵].
Select "Diagnostic" and confirm with [↵].
2. Select "Drag pointer" and confirm with [↵].
3. Select "P min/max" and confirm with [↵].
4. Select "display" and confirm with [↵].
» Limit values are displayed.
P
= P
min
P
= P
max
WIKA operating instructions, model DMSU21A
/P
min
max
EN