To ensure functional reliability, operate the valve with
the coil installed ex works only!
Note the voltage and current type as specified on
the label. Voltage tolerance ±10 %
Valves with flange body:
Danger!
Risk of electric shock if the protective conductor
function is defective!
•
After installing the coil, check the function of the
protective conductor.
→
Check function of the protective conductor.
Resistance
Test voltage
max. 0.1 Ω
12 V
Connection to cable plug:
Danger!
Risk of electric shock if protective conductor not
connected!
•
Always connect protective conductor!
Earthing connection (if fitted): Middle spade connection
english
28
9.
mainTenance,
TrOubleshOOTing
The valve is maintenance-free under normal operating
conditions.
9.1.
safety instructions
Danger!
Risk of injury from high pressure in the equipment!
•
Before loosening the pipes and valves, turn off the
pressure and vent the pipes.
Risk of injury due to electrical shock!
•
Before reaching into the device or the equipment,
switch off the power supply and secure to prevent
reactivation!
•
Observe applicable accident prevention and safety
regulations for electrical equipment!
english
30
Test current
1 A
Ensure that the seal is seated correctly for the
electrical connection to the cable plug.
Seal
Valve
note!
If the tightening torque is too great, the device may
be damaged!
•
Observe the maximum tightening torque of the screws!
→
Screw cable plug to the valve at a maximum tightening
torque of 0.4 Nm.
Warning!
Risk of injury from improper maintenance!
•
Maintenance may be carried out by authorized techni-
cians only and with the appropriate tools!
Risk of injury from unintentional activation of the
system and an uncontrolled restart!
•
Secure system from unintentional activation.
•
Following maintenance, ensure a controlled restart.
9.2.
maintenance Work
Malfunctions
If malfunctions occur, check
→
the port connections: the correct configuration of the
fluid connections according to the circuit functions (see
chapter entitled "8.2. Fluid Installation").
→
whether the operating pressure is within the permitted
range.
→
the power supply and valve control.
→
flange connection: check the location of the sealing.
If the valve still does not switch, please contact your
Bürkert Service.