ELMON relay 32-312
Safety Relay
V1.0: If no error is present, then LED Power shows the function control (briefly off).
V2.1 and later: If no error is present, then LED Power shows the operating state (on).
During the output of an error message, the number of output pulses indicates the error:
Pulse
Error message
1
Voltage supply outside of the valid value range
2
ELMON inductive transmission error
3
Output control Open faulty
4
Output control Close faulty
5
Data transmission between microcontrollers faulty
6
Testing sensor input faulty ( stationary contact edges) (Open/Close)
6.3 Connection terminals
STOP Opening
STOP Closing
STATIONARY Opening
STATIONARY Closing
Transmit
24 V AC/DC
L1 N
7. Mechanical mounting
The switching unit is to be professionally mounted at a suitable location. After removing the cover, the housing
can be mounted with four screws.
Do not install the switching unit in the immediate vicinity of strong sources of heat.
The switching unit may be mounted in any orientation. To prevent moisture penetration, it should, however,
be installed so that the cable conduits point downward.
Control circuit (emergency-off)
Stop, direction of movement - Opening (channel 1)
Control circuit (emergency-off)
Stop, direction of movement - Closing (channel 2)
Sensor input
Direction of movement - Opening (channel 1)
Sensor input
Direction of movement - Closing (channel 2)
No assignment
Supply voltage 24 V AC/DC
Supply voltage 230 V 50/60 Hz
17