Safety Relay

9. Commissioning and functional test

The plant / machine must be tested for proper function after all of the electrical connections have been
established and the supply voltage has been turned on:
• Actuate the sensors in sequence
• Check the switching units for proper reaction
The safety system must be professionally inspected at appropriate intervals. The inspection must be docu-
mented in such a way as to be comprehensible at all times.
The requirements of the plant/machine manufacturer are to be taken into account and followed.

10. Error diagnosis

Only the green LED may illuminate if the supply voltage has been correctly connected . If one of the red LEDs
illuminate, there is an error in the system which can be pinpointed with the aid of the LED.
LED
LED's are not
The supply voltage is missing, too low
illuminated
or has been connected incorrectly
Green LED flashes
Internal error is indicated by the
cyclically
number of pulses
A single red LED
Contact edge(s) not connected,
is illuminated
connected incorrectly or faulty
One of the contact edge connections
is not being used
* If the error is not in the wiring, the function of the electronics can be tested by connecting an 8.2 kΩ
resistor to the respective SCE input on the switching unit.
If the electronics work perfectly after performing the test, the sensor must be checked using an ohmmeter.
To do this, the connection of the sensor to the switching unit must be disconnected and connected to
an ohmmeter. The resistance must be 8.2 kΩ ±500 Ω when the sensor is inactive and must not exceed
500 Ω when the sensor is active.

11. Taking out of service and disposal

The products manufactured by ASO are intended solely for commercial use (B2B). At the end of use, the
products are to be disposed of according to all local, regional and national regulations. Products can also be
returned to ASO, which will then dispose of them properly.
20
Error
Check connections and supply voltage.
According to the error indicator, switch off
the output, switch off the device or check the
supply voltage .
- Check the connections of the corresponding
sensors (squeezed or brittle supply lines, etc.)
- Check sensors *
- Check safety contact edge(s)*
Any contact edge connections that are not
being used must be permanently bridged
using one of the supplied 8.2 kΩ resistors

Error correction