Step. 5 Remove the (2) screws indicated in the
image and slide the entire fan assembly out
from the cabinet.
Step. 6 Rotate the blower assembly 180°. The
motor should now be on the opposite side.
Specifications are subject to change without notice.
SVZ-KP12, 18, 24, 30, 36NA
Motor on left
Step. 7 Reinsert the blower assembly with the
motor now on the left into the air handler cabinet
and reuse the (2) screws that secured the fan
assembly in position. Reroute the connector for
the motor back into the enclosure and reconnect.
Reinstall Control Box.
The wiring harness might have to be removed
from the plastic retainers mounted to the mo-
tor bracket in order to have sufficient length to
reach the electrical enclosure mounted to the
fan assembly. Ensure wiring harness is secure
so it cannot be pulled into the fan.
Step. 8
A. Disconnect the waterproof thermistor har-
ness inside the coil portion of the cabinet.
B. Remove the brackets which secure the coil
assembly.
C. Slide the coil assembly out of the air handler
cabinet.
16
NOTE
© 2024 Mitsubishi Electric US, Inc.