7.3 Assembly diagram
1) For correct installation, all the joints of the flue
gas ducting between the fireplace and the
flue must be sealed.
2) Cladding in ceramic fibre or rock wool with ex-
ternal aluminium foil.
3) Rear external air intake, ensure a minimum
distance of 5 cm between cladding and com-
bustion air intake pipe.
4) The lining must be made of fireproof material.
5) Min distance. 1 cm between cladding and fire-
place stove.
6) Protect any wooden parts with fireproof
material.
7) Counter-hood
and
structure.
8) Pellet loading system. See the instructions
supplied with the kit for installation.
9) UNI standards require the installation of a
heat recovery grille as close as possible to the
ceiling.
9
8
7
6
5
4
004779216 - 18/09/2024
ITALIANO
ENGLISH
fireproof
load-bearing
1
2
3
Fig. 30
FRANÇAIS
7.4 Hydraulic system
Connection to the hydraulic system and the
system itself must be performed by qualified
personnel, in compliance with the laws and reg-
ulations in force in the country of installation.
The appliance is supplied with everything neces-
sary for installation on the heating system.
Make sure that all the control and safety devices
have been installed correctly, including those
supplied (safety valves and thermal discharge).
MAXIMUM OPERATING PRESSURE: 2.5 bar.
The system must be designed in such a
way as to absorb the minimum power
of the appliance in any operating
condition.
It is good practice to clean the system
before rendering it operative.
In order to always ensure high efficiency and
durability of the appliance, it is recommended,
in the presence of hard water (18-30 °F), to use a
softener. If necessary use an anti-algae additive
for the technical water.
7.4.1 Hydraulic connections
• Connect the appliance to the heating system
by means of the flow (A) and return hoses (B).
• Set up a non-returnable drain pipe, of suitable
diameter, to which to connect the drain of the
safety valve (C).
A
DEUTSCH
ESPAÑOL
C
B
Fig. 31
69