8.10.
Acyclic data format
8.10.1. Errors data CPUx format
Name
Module
Error code
Error address
Firmware version (x.y in hexadecimal format)
Extended code 0 (optional)
Extended code 1 (optional)
The Module field is defined as follow:
B7-B2
B1-B0
Module name
Node
The subfield Module name is defined as follow:
Name
Code
CE-AC-FI8FO2
2
CE-AC-FO2
3
CE-FI16
4
CE-FI8
5
CE-AC-FO4
6
CE-FM4
7
CE-SPM2
8
CE-SPM1
9
For the Error code field please refer to the EUCHNER manual Dok.-Nr. 2121331 "Operating Instructions Installation and Use
Modular Safety Control System MSC".
8.10.2. Input diagnostics format
Name
Diagnostic index
Diagnostic code
A maximum of 16 Input diagnostics are transferred, if more diagnostics are present on the system only the first 16 are
available on the fieldbus.
8.10.3. OSSD diagnostics format
Name
Diagnostic index
Diagnostic code
A maximum of 16 OSSD diagnostics are transferred, if more diagnostics are present on the system only the first 16 are
available on the fieldbus.
8.10.4. Project CRC format
Name
CRC byte 0
CRC byte 1
54
Size
UINT8
UINT8
UINT32
UINT8
UINT8
UINT8
Name
Code
CE-SPM0
10
CE-AZ-FO4
11
CE-AZ-FO4O8
12
CE-O8
13
CE-O16
14
CE-AH-FO4SO8
15
CE-AC-FI8FO4S
17
Size
UINT8
UINT8
Size
UINT8
UINT8
Size
UINT8
UINT8
(trad. mode d'emploi d'origine) 2121341-09-12/23