Step 11.
Configure the rotary switch to set the Max. output current. Default
factory setting is 48A.
a.
Turn OFF power.
b.
Use a flathead screwdriver to adjust the rotary switch configuration appro-
priate for the installed circuit breaker.
Table 4.1 Rotary Switch Configuration
Rotary Switch Configuration
If the charger is installed on a circuit breaker smaller than 60A, the rotary switch
should be adjusted to limit charger output to less than or equal to 80% of the cir-
cuit breakers rating. (E.g.: For a 40A circuit breaker, the charger output limit should
be adjusted to no more than 32A.) If needed, Amperage Reduction Labels are avai-
lable to place on charger and circuit breaker.
c.
Confirm the output current on the bottom of the LCD screen after cover is
reinstalled and charger is powered ON.
Figure 4.13 Rotary Switch Location
Maximum Output Current
0
1
2
3
4
5
12A
16A
24A
32A
40A
48A
30
Installation Manual
Circuit Breaker
15A
20A
30A
40A
50A
60A