3 Configuration d'un système PROFIBUS-DP
;
;
Freeze_Mode_supp = 0
Sync_Mode_supp = 0
Auto_Baud_supp = 1
Set_Slave_Add_supp = 1
Min_Slave_Intervall = 6
Modular_Station = 1
Max_Module = 4
Max_Diag_Data_Len = 6
Slave_Family = 5
;
;
;
;
;This lines are for locating PBC file, and initial data length.
;Do not disturb!!!
;atPBC_File = C:\PROGRAMME\JUMO\GSDGEN\14401XX\D\ju_d300.PBC
;atINIT_LEN = 2
;
User_Prm_Data_Len = 16
User_Prm_Data = 0x00, 0x03, 0x02, 0x01, 0x13, 0x00, 0x43, 0x04, 0x17, 0x20, \
0x10, 0x08, 0x27, 0x20, 0x00, 0x08
Max_Input_Len = 13
Max_Output_Len = 8
Max_Data_Len = 21
;==================== Input Master ========================================
Module = "Interface Mode" 0x10
Preset = 1
Endmodule
Module = "Regler/Istwert" 0x13
Preset = 1
Endmodule
Module = "azykl. Daten/Block-Read" 0x17
Preset = 1
Endmodule
;==================== Output Master ========================================
Module = "azykl. Daten/Block-Write" 0x27
Preset = 1
Endmodule
;*** Slave specific values ***
;Freeze-mode is not supported
;Sync-mode is not supported
;Automatic recognition of baudrate
;Set_Slave_Add is supported
;Slave-Interval = 0.6 ms
;Modular station
;
;
;*** Parameterization ***
La structure de ce fichier GSD est pré-
vue pour installation sur le SIMATIC S7
(société SIEMENS).
Si des problèmes d'installation appa-
raissent pour d'autres commandes, il
faut mettre à zéro tous les enregistre-
ments Preset=1.
Dans ce cas, il faut en plus placer dans
le bon ordre sur la représentation gra-
phique du process de l'API les varia-
bles sélectionnées dans le générateur
GSD.