6.1 Arrangement of smoke detectors in corridors and
hallways and in special spatial geometries
In corridors and hallways with a minimum width of < 1 m, the smoke
detector should be mounted in the middle of the ceiling.
In corridors and hallways with a maximum width of 3 m, the distance
between two smoke detectors must not exceed 15 m. The distance to
the front sides of the corridor must not exceed 7.5 m.
Wall
Straight corridor or hallway
Rectangular corridor or hallway
In large corridors and hallways
In corner areas
42