minimum mantel clearances
Combustible mantel clearance can vary according to the mantel depth. Use the graph to help evaluate the
clearance needed. These same requirements apply to any combustibles protruding on either side of the
appliance.
26
24
22
20
M
H
18
A
E
16
N
I
14
T
G
12
E
H
10
L
T
8
6
4
0
1 2
3 4
MANTEL DEPTH
MANTEL DIMENSIONS
Ref
Height
A
31 5/8" (803mm)
5" (127mm)
B
C
7" (178mm)
9" (229mm)
D
E
11" (279mm)
ONLY IF THE UNIVERSAL HEAT MANAGEMENT SYSTEM IS
INSTALLED, MANTEL CLEARANCES CAN BE REDUCED.
24
22
20
18
16
M
H
14
A
E
12
N
I
10
T
G
8
E
H
L
T
6
4
2
0
2 4 6 8 10 12 14 16 18 20 22
MANTEL DEPTH
WARNING
!
Risk of fire! Reduced mantel clearances are ONLY acceptable for applications with UHM installed.
*Mantel depth must be appropriately sized if placing any valuable items above the fireplace / mantel (see
"clearances around appliance (TV and valuable objects)").
56
W415-4150 / A-0 / 05.23.24
5 6
7
8
9
10
Depth
N/A
2" (51mm)
4" (102mm)
6" (152mm)
8" (203mm)
D
C
B
Hood
MANTEL DIMENSIONS (WITH UHM)
Ref
Height
A
31 5/8" (803mm)
0" (0mm)
B
C
2" (51mm)
4" (102mm)
D
E
6" (152mm)
E
Appliance
Opening
A
Depth*
N/A
12" (305mm)
14" (356mm)
16" (406mm)
18" (457mm)