Télécharger Imprimer la page

Hitachi AIR CORE 700 PPIM-B18UFA1DQ Manuel D'utilisation, D'installation Et D'entretien page 10

Masquer les pouces Voir aussi pour AIR CORE 700 PPIM-B18UFA1DQ:

Publicité

Les langues disponibles

Les langues disponibles

manufacturer if in doubt. In addition, a set of calibrated weighing scales shall be available and in good
working order. Hoses shall be complete with leak-free disconnect couplings and in good condition.
The recovered refrigerant shall be processed according to local legislation in the correct recovery
cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in recovery units and
especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to an
acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The
compressor body shall not be heated by an open flame or other ignition sources to accelerate this
process. Draining of oil from a system shall be carried out safely.
Disposal of equipment shall follow the national regulations.
The storage of the appliance should be in accordance with the applicable regulations or instructions,
whichever is more stringent.
The maximum number of pieces of equipment permitted to be stored together notes by each product
package information and standard following ISO 780-2015.
After completing the installation work, check that the refrigerant gas does not leak throughout the system.
When installing the unit in a small room, take measures to keep the refrigerant concentration from
exceeding allowable safety limits. Excessive refrigerant leaks, in the event of an accident in a closed
ambient space, can lead to oxygen deficiency.
When installing or relocating the air conditioner, do not let any other substances besides R32, such as
air, enter the refrigerant circuit. The presence of air or foreign matter in the refrigerant circuit causes an
abnormal pressure rise, which may result in equipment damage and even injury.
Refrigerant R32 in the system must be kept clean, dry, and tight.
○ Clean and Dry -- Foreign materials (including mineral oils such as SUNISO oil or moisture) should be
prevented from getting into the system.
○ Tight -- R32 does not contain any chlorine, does not destroy the ozone layer, and does not reduce the
earth's protection again harmful ultraviolet radiation. R32 can contribute to the greenhouse effect if
it is released.
Only use tools for R32, such as a gauge manifold, charge hose, gas leak detector, reverse flow check
valve, refrigerant charge base, vacuum gauge, or refrigerant recovery equipment.
If the conventional refrigerant and refrigerator oil are mixed in R32, the refrigerant may deteriorate.
For Ducts indoor units, it shall not contain a potential ignition source in the duct system, such as
electrical heating.
For Duct indoor units, when connected via an air duct system to one or more rooms, the supply and
return air shall be directly ducted to the space. Open areas such as false ceilings shall not be used as a
return air duct.
Duct indoor units that connected via an air duct system to one or more rooms, auxiliary devices which
can be a potential ignition source shall not be installed in the ductwork. Examples of such potential
ignition sources are hot surfaces and electric switching devices.
Duct indoor units that connected via an air duct system to one or more rooms are installed in a
room with an area less than A
operating open flames (for example an operating gas appliance) or other potential ignition sources (for
example an operating electric heater, hot surfaces). A flame-producing device may be installed in the
same space if the device is provided with an effective flame arrestor.
Appliance shall be installed, operated and stored in a room with a floor area larger than A
- see table below].
The installation of pipe-work shall be kept to a room with a floor area larger than A
table below].
The unit has requirements on the minimum required room area (A
charging amount (m). The total amount of refrigerant charged in the system corresponds to the room
area installed in the table below. The calculation result is based on the Ducted-mounted unit, and the
2
[A
(m
) - see table below], that room shall be without continuously
min
min
-ix-
min
2
(m
) [A
min
) used with different refrigerant
min
2
2
(m
) [A
(m
)
min
2
(m
) - see
min

Publicité

loading