Precautions for R32
This air conditioner uses R32 flammable refrigerant. Air conditioner with R32 refrigerant, if not be
treated carefully, may cause serious harm to the human body or surrounding things. Please read the
following instructions carefully before installing, using and maintaining.
WARNING
!
Do not use means to accelerate the defrosting process or to clean, other than those recommended by
the manufacturer.
The appliance shall be stored in a room without continuously operating ignition sources (for example:
open flames, an operating gas appliance or an operating electric heater).
Do not pierce or burn the refrigerant system to avoid the leakage.
Be aware that refrigerants might not contain an odour.
Do not charge R32 into system other than those designated for R32.
Do not charge R32 system with oil other than those designated for R32.
Do not use a reclaim cylinder other than an R32 reclaim cylinder.
Be sure to only use refrigerant piping approved for use with R32 refrigerant. The use of unapproved
piping may result in explosive rupture.
The pipe-work shall be securely mounted and guarded from physical damage.
The national gas regulations shall also be observed when field-installed refrigerant pipes are required.
Field-made refrigerant joints indoors shall be tightness tested. The test method shall have a sensitivity
of 0.01lbs (5 grams) per year of refrigerant or better under a pressure of at least 0,25 times the
maximum allowable pressure. No leak shall be detected; Mechanical connections shall be accessible for
maintenance purposes.
The joints shall not be reused, unless after re-flaring the pipe.
Joints made in the installation between parts of the refrigerating system, with outdoor part charged,
shall be made in accordance with the following.
○ A brazed, welded, or mechanical connection shall be made before opening the valves to permit
refrigerant to flow between the refrigerating system parts. A vacuum valve shall be provided to
evacuate the interconnecting pipe and/or any uncharged refrigerating system part.
○ Mechanical connectors used indoors shall comply with ISO 14903. When mechanical connectors are
reused indoors, sealing parts shall be renewed. When flared joints are reused indoors, the flare part
shall be re-fabricated.
○ Refrigerant tubing shall be protected or enclosed to avoid damage.
That after completion of field piping for split systems, the field pipework shall be pressure tested
with an inert gas and then vacuum tested prior to refrigerant charging, according to the following
requirements:
○ The minimum test pressure for the low side of the system shall be the low side design pressure and
the minimum test pressure for the high side of the system shall be the high side design pressure,
unless the high side of the system, cannot be isolated from the low side of the system in which case
the entire system shall be pressure tested to the low side design pressure.
The appliance shall be stored in a well-ventilated area where the room size corresponds to the room
area as specified.
The appliances are designed for use at altitudes less than 6561.6ft (2000m), may cause serious harm to
the human body or surrounding things if used at altitudes 6561.6ft (2000m) and above.
Keep any required ventilation openings clear of obstruction, don't block air inlet or air outlet,
Otherwise, the cooling or heating capacity will be weakened, even cause system stop operating or
safety hazard.
Maintenance or repair of air conditioner using R32 refrigerant must be carried out after security check
to minimize risk of incidents.