Check to ensure that the voltage of power supply is within 10% of nominal voltage and earth phase is
•
contained in the power supply wires. If not, electrical parts will be damaged.
•
Check to ensure that the capacity of power supply is enough. If not, the compressor will not be able to
operate because of abnormal voltage drop at starting.
•
Check to ensure that the earth wire is connected.
•
Install a main switch, multi-pole main switch with a space of 1.38 inch (3.5mm) or more, single phase
main switch with a space of 1.18 inch (3.0mm) or more between phases.
Check to ensure that the electrical resistance is more than 2MΩ, by measuring the resistance between
•
ground and the terminal of the electrical parts. If not, do not operate the system until the electrical
leakage is found and repaired.
Electrical wiring diagram
Model
PAS-09BUFASDQ1
208/230V~, 60Hz
PAS-12BUFASDQ1
208/230V~, 60Hz
PAS-18BUFASDQ1
208/230V~, 60Hz
PAS-24BUFASDQ1
208/230V~, 60Hz
PAS-30BUFASDQ1
208/230V~, 60Hz
PAS-36BUFASDQ1
208/230V~, 60Hz
PAS-48BUFASDQ1
208/230V~, 60Hz
Max Running Current (A): REFER TO NAMEPLATE
NOTES:
•
The ground wire must be longer than the current-carrying conductor when installing the power cord.
•
The wiring specifications of the weak current communication loop should not be less than RVV(S)P
shielded wire or equivalent, the shielding layer needs to be grounded.
•
Using the air conditioner power terminal to transfer the power cord is strictly prohibited
•
Follow local codes and regulations when selecting field wires, and all the above are the minimum wire
size.
•
Power cord selection shall not be lighter than polychloroprene sheathed flexible cord (code
designation 60245 IEC 57), and the power cord should be copper wire.
•
The wire sizes marked with *1 in the above table are selected at the maximum current of the unit
according to IEC60335-1 Standard.
•
When transmission cable is longer than 49.2ft (15m), a larger wire size should be selected.
•
Install main switch and ELB for each system separately. Select the high response type ELB that is
acted within 0.1 second.
•
In the case that power cables are connected in series, add each unit maximum current and select
wires below.
Rated current of appliance (A)
> 0.2 and ≤16
> 16 and ≤25
> 25 and ≤32
> 32 and ≤40
> 40 and ≤63
Max
Power
Running
supply
Current
(A)
7.5
9.5
13.5
16.0
24.2
27.9
29.1
-19-
4. Installation Instructions
ELB
Rated
Nominal
current
sensitive
(A)
current (mA)
12
30
12
30
20
30
20
30
32
30
32
30
32
30
Nominal cross-sectional area (mm²)
Power source
Transmission
cable size
cable size
*1
IEC 60335-1
IEC 60335-1
3×2.5mm²
2×0.75mm²
3×2.5mm²
2×0.75mm²
3×2.5mm²
2×0.75mm²
3×2.5mm²
2×0.75mm²
3×4mm²
2×0.75mm²
3×4mm²
2×0.75mm²
3×4mm²
2×0.75mm²
1.5
2.5
4
6
10
*1