Télécharger Imprimer la page

Hitachi AIR CORE 700 PAS-09BUFASDQ1 Manuel D'installation Et D'entretien page 21

Publicité

Les langues disponibles

Les langues disponibles

Fix the end of piping tape with adhesive tape.
When piping has to be arranged through above
ceiling, closet or area where temperature and
humidity are high, use wind additional commercially
sold insulation for prevention of condensation.
5. Air tight test
Do use Nitrogen
Connect the gauge manifold using charging hoses with
a nitrogen cylinder to check joints of the liquid line and
the gas line stop valves.
Perform the air tight test.
Don't open the gas line stop valves.
Apply nitrogen gas pressure of 602psig (4.15MPa).
Check any gas leakage at flare nut connections,
or brazed parts by gas leak detector or foaming
agent.
It is OK if gas pressure doesn't decrease.
After the air tight test, release nitrogen gas.
6. Vacuum pumping and charge refrigerant
Vacuum pumping
(1) Remove the service port cap of the stop valve on the gas pipe side of the outdoor unit.
(2) Connect the manifold gauge and vacuum pump to the service port of the stop valve on the gas pipe
side of the outdoor unit.
(3) Run the vacuum pump. (Work for more than 15 minutes.)
(4) Check the vacuum with the gauge manifold valve, then close
the gauge manifold valve and stop the vacuum pump.
(5) Leave it as is for one or two minutes. Make sure that the
pointer of the manifold gauge remains in the same position.
Confirm that the pressure gauge shows -14.7psig (-0.101MPa or
-760mmHg).
(6) Remove the manifold gauge quickly from the service port of
the stop valve.
(7) After refrigerant pipes are connected and evacuated, fully
open all stop valves on both sides of gas pipe and liquid pipe.
(8) Tighten the cap to the service port.
(9) Retighten the cap.
(10) Leak test foam with halogen leak detector to check the flare
nut and brazing leaks. Use foam that does not generate
ammonia (NH
) in the reaction.
3
CAUTION
!
An excess or a shortage of refrigerant is the main cause of trouble to the unit. Charge the correct
quantity of refrigerant according to the description in the manual.
Check refrigerant leakage in detail. If a large refrigerant leakage occurs, it will cause difficulty in
breathing or harmful gas will occur if a fire is being used in the room.
4. Installation Instructions
Tightening torque for
Clamp
Piping insulation procedure
Procedure
Connect
Fill
refrigerant pipe
Nitrogen Gas
F i g.9. 2
Pressure gauge
Manifold
valve
-17-
nut
Insulation
Refrigerant pipe
Insulation
Check of pressure
Pass
Decrease
Repairing of
Leakage part
Indoor unit
Outdoor unit
Charge hose
(for R32)
Vacuum pump

Publicité

loading