5.1.2
Configuring the RS485 board microswitch
The 3rd pole of the switch connects the end-of-line resistor on the RS485 bus. Positions 1 and 2
activate the pull-up and pull-down resistors for devices with a Standard uncertainty threshold.
The RS485 board must have one of the following two configurations:
-
The three poles in position ON.
-
Poles 1 and 2 in position OFF. Pole 3 in position ON.
5.1.3
Installation on the FUSION
The RS485 board connects to the lower slot on the control board.
24
Connection position of the RS485 kit on the FUSION control board.