ENGLISH
Caution - Warning
Before doing any work, cut off the mains elec-
tricity supply.
The manufacturer has tested the appliance
with its own mains gas, identifi ed by the sticker
applied to the nameplate.
If the type of gas to be connected is diff erent
from that used for testing, proceed as follows.
Turn off the gas supply tap (A).
1)
Disconnect the electricity supply.
2)
Replace the burner nozzle (see page 13).
3)
Replace the pilot light injector (see page14).
4)
Remove the testing gas sticker from the name-
5)
plate (B) and apply the new one to identify the
gas being used.
Remove the sticker from the appliance and ap-
6)
ply the new one (C) with the category of the
country of installation.
Important
On completion of the operation, make sure
that there are no gas leaks or malfunctions.
Important
Before it is put into service, the system must
be tested to check the operating conditions
of every single component and identify any
malfunctions. In this stage, it is important to
check that all health and safety requirements
have been complied with in full.
To test the system, make the following checks:
Turn on the gas supply tap and check that the
1)
connections are right;
Check that the mains gas is the same as that
2)
used for commissioning of the appliance,
and carry out the conversion procedure if
necessary (see page 12);
12
CONVERSION OF GAS SUPPLY
C
AL
AL
AT
AT
BE
BE
BE
BE
BG
BG
B
TESTING OF THE APPLIANCE
3)
4)
5)
6)
After testing, if necessary instruct the user in all
the skills necessary for putting the appliance into
operation in conditions of safety, in accordance
with legal requirements.
HANDLING AND INSTALLATION
II2H3B/P: G20/20mbar, G30/30mbar
II2H3+: G20/20mbar, G30-G31/28_30-37mbar
3P
II2H3B/P: G20/20mbar, G30/50mbar
II2H3P: G20/20mbar, G31/50mbar
II2E+3+: G20-G25/20-25mbar, G30-G31/28_30-37mbar
II2E+3B/P: G20-G25/20-25mbar, G30/30mbar
II2E+3P: G20-G25/20-25mbar, G31/37mbar
II2E+3B: G20-G25/20-25mbar, G30/30mbar
II2H3B/P: G20/20mbar, G30/30mbar
II2H3+: G20/20mbar, G30-G31/28_30-37mbar
G20
m3/h
mbar
G31
kW
G25
kW
m3/h
mbar
G30
kW
Kg/h
mbar
G20
m3/h
mbar
G31
kW
G25
kW
m3/h
mbar
G30
kW
Kg/h
mbar
Check that the burner is switching on correctly
and its combustion;
Check that the safety thermocouple is working
correctly;
Check that there are no gas leaks;
Check that the nameplates specify the correct
gas for the country of use.
IS
II2H3B/P: G20/20mbar, G30/30mbar
IS
II2H3+: G20/20mbar, G30-G31/28_30-37m
IT
II2H3+: G20/20mbar, G30-G31/28_30-37m
IT
II2H3B/P: G20/20mbar, G30/30mbar
IT
II2H3P: G20/20mbar, G31/37mbar
LT
II2H3+: G20/20mbar, G30-G31/28_30-37m
LT
II2H3B/P: G20/20mbar, G30/30mbar
LT
II2H3P: G20/20mbar, G31/37mbar
LU
II2H3B/P: G20/20mbar, G30/30mbar
LU
II2H3+: G20/20mbar, G30-G31/28_30-37m
A
mbar
kW
Kg/h
~
~
TYPE
mbar
kW
Kg/h
~
~
TYPE
3413720_inst_GB
01
rif
0051
~
CE n
01
rif.
0051
~
CE n.