Control drawing A5E52688321A/001
Ratings
Table 14: SITRANS FCT0x0 – Transmitter
Hazardous locations
(United States)
Hazardous locations
(Canada)
Ambient Temperature range
Enclosure Rating
Temperature code
Table 15: SITRASN FCSx00 – Sensor
Hazardous locations
(United States)
Hazardous locations
(Canada)
Ambient Temperature range
Enclosure Rating
Temperature code
Class I, Division 1, Groups A, B, C, D, T6
Class II, Division 1, Groups E, F, G, T6
Class III, Division 1
or
Class I, Zone 1, Gr. IIC/IIB
Intrinsically safe connections for Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G, T6
[Ex ia Ga] IIC T6
Associated Apparatus
Class I, II, III, Division 1, Groups A, B, C, D, E, F, G T6
[Ex ia Ga] IIC T6 in accordance with Table 9
Class I, Division 1, Groups A, B, C, D, T6
Class II, Division 1, Groups E, F, G, T6
Class III, Division 1
or
Zone 1, Gr. IIC/IIB per CEC 18-100 & 18-090
Intrinsically safe connections for Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G T6
[Ex ia Ga] IIC T6
Associated Apparatus
Class I, II, III, Division 1, Groups A, B, C, D, E, F, G T6
[Ex ia Ga] IIC T6 in accordance with Table 9
-40°C ≤ Ta ≤ 60°C
Enclosure Type 4X
IP66/ IP67
in accordance with Table 2 or/ and see Table 18 to Ambient
temperature for:Table 27
Class I, Division 1, Groups A, B, C, D, T6
Class II, Division 1, Groups E, F, G, T6
Class III, Division 1
or
Ex ia IIC Ga T6
Class I, Division 1, Groups A, B, C, D, T6
Class II, Division 1, Groups E, F, G, T6
Class III, Division 1
or
Ex ia IIC Ga T6 per CEC 18-100 & 18-090
-50°C ≤ Ta ≤ 80°C
Enclosure Type 4X
IP66/ IP67
in accordance with Table 2 or/ and see Table 18 to Ambient
temperature for:Table 27
(only for option F42)
(only for option F42)
15