Step 6: Electrical Requirements, Connection & Grounding
Dual Fuel models
must be connected
to the power
supply utilizing
one of the following
methods.
For all
methods
of connection,
the length of the cord or conduit/wiring
must allow the unit to be slid completely
out
of the cabinet without
having to unplug or disconnect
the unit from the power supply, Recommended
minimum
free length of cord or conduit is four feet, Electrical
installations
and grounding
must be in accordance
with all
local codes and ordinances,
and/or the National
Electric
Code, as applicable,
4-CONDUCTOR
CORD
NORMALLY,
A UNIT
MUST
BE CONNECTED
TO
THE
POWER
SUPPLY
WroTH A 3-
4-CONDUCTOR
CORD
KIT
RATED
125/250
VOLTS,
50 AMPERES,
AND
MARKED
FOR
USE
WITH
RANGES.
The cord kit must
be attached
to the range junc-
tion boxwith a strain reliefwMch
will fit a 1" diameter
hole. If not
already
equipped,
the
cord
must have 1/4" faston
closed-
loop lugs attached
to the free
ends of the individual conduc-
tors,
preferably
soldered
in
place.
PERMANENT
CONNECTION
(HARD
WIRING)-
Units
may
be hard wired
to the power
supply.
The
installer
must
provide
approved
flexible
aluminum
conduit,
3/4" trade
size,
maximum
6 feet
long.
Locate the junction
box on the
rear of the unit and remove
cover. Refer to Fig.8. Remove
the
ground
strap
retaining
screw
and bend
the ground
strap up. Refer to Fig. 9. The
conduit must be installed to the
junction box using an approved
conduit
connector.
Wiring
for the
unit
is to be
brought
into the junction
box
through the conduit.
The ends
of
the
wiring
must
have
1/4" faston
closed-loop
lugs
attached,
preferably
soldered
in place. Make the connections
to the terminal
block provided.
Secure the ground lead to the
junction
box with
the screw
previously
used to secure the
ground strap. Refer to Fig. 11.
The free
end of the conduit
must be connected
to a junc-
tion box provided
in the gas
and electrical
supply zone, as
shown in Figure 3Aon Page 7.
3-CONDUCTOR
CORD
-
WHERE LOCAL
CODES AND
ORDINANCES
PERMRT
GROUNDING
THROUGH
NEUTRAL,
AND
CONVER-
SION
OF
SUPPLY
TO
4
WmRE
mS iMPRACTiCAL,
UNIT MAY BE CONNECTED
TO
THE
POWER
SUPPLY
WITH
A
3-CONDUCTOR
CORD
KIT
RATED
125/250
VOLTS,
50
AMPERES,
AND
MARKED
FOR
USE
WITH
RANGES.
FIG.
8 - Location
of Junction
Box on dual fuel
ranges
GAS SUPPLY
JUNCTION
BOX
/
Flexible
electrical
conduit
or
4-connector
Appliance
Cord
The cord kit must be attached
to the range junction
box with a
strain
relief which
will fit a 1"
diameter
hole.
If not already
equipped,
the cord must have
1/4" faston closed-loop
lugs at-
tached to the free ends of the
individual
conductors,
prefer-
ably soldered
in place.
Installer
- show the owner the location of the circuit breaker
or fuse. Mark it for easy reference.