The installation must be carried out according to
local regulations and directives.
Please note that all Sololift+ models must be
accessible for maintenance and repair. Engineers
will not be able to carry out service or repair of the
unit without easy access.
3.1 Electrical installation
The electrical installation must only be carried
out by trained personnel.
Sololift+ CWC-3 must be connected to a voltage
supply according to the nameplate.
The installation must include an earth
leakage circuit breaker for protection
against earth fault currents. This
ensures protection when using a
Schuko plug or another alternative to a
plug with earth pin.
Sololift+ CWC-3 must be connected to a
mains switch with a minimum contact
gap of 3 mm in all poles.
The lifting station must be protected
against water splashes in accordance
with regulations.
3.1.1 Wiring diagram
Rp
C
Ra
Fig. 4
3.1.2 Motor protection
In case of overtemperature a thermal
overload switch cuts out the motor and
cuts it in when the motor has cooled
sufficiently.
3.2 Mechanical installation
The floor fittings F must be fitted to prevent uplift in
case the room is flooded. Sololift+ CWC-3 should be
installed with adequate access for maintenance.
3.2.1 Siphoning
If the connection to the sewer is below the bottom of
the lifting station, it is advisable to install a vent valve
to prevent siphonage.
If the last pipe section after a horizontal discharge
pipe is vertical, it must be two sizes bigger than the
horizontal pipe. If the horizontal pipe is ∅23, the
vertical pipe should be ∅40. If the horizontal pipe is
∅32, the vertical pipe should be ∅50. See fig. 5.
Fig. 5
3.2.2 Application sketch
Fig. 6
3.2.3 Dimensions of hollow space
The drawing show the dimensions of the hollow
space for the Sololift+ CWC-3.
600 mm
Fig. 7
3.2.4 Access to hollow space
The hollow space must be covered by a 500 x
400 mm plate. It should be possible to remove the
plate only by means of tools.
min. 190 mm
9