Models
Available powers (kVA / kW)
Output short circuit current
Short circuit current in Normal mode (RMS)
Short circuit current in Normal mode (Peak)
Normal / Battery mode (peak)
Batteries
Battery voltage
Number of batteries
Rated voltage and capacity (Ah) per element
EBM maximum amount
Maximum battery capacity (Ah)
EBM auto-detection
Hot swappable battery
Charger
Charging method
Charging current
Recharge time
Other functions
Frequency converter (CVCF)
General
Display
Language
USB port
RS232 port
Dry in/out
RPO (Remote Power Off)
Optional cards (for insertion into a slot)
HDMI port (wireless)
IoT Ethernet port
Monitoring software
Dimensions (F x W x H mm.)
IP protection
Wheels
Working temperature
Storage temperature (with battery)
Storage temperature (no battery)
Relative humidity
Working altitude
Acoustic noise at 1 m.
Safety
Electromagnetic compatibility (EMC)
Operation
Marking
Quality System
Dimension from the mounting ear to the most protruding part of the front face.
(1)
Tab. 23. General technical specifications.
88
4
5
54 A for 200 ms max.
20 A/100 ms
80 A
16 x 12 V @ 7 Ah
1.4 A (adjustable 0 ÷ 4 A)
3 hours at 90%
1 programmable dry in; 1 programmable dry out
Interface to relays, SNMP, Internet or Intranet
TWIN RT3 :
B0/B1: (570+35
)*438*86,3 (2U)
(1)
EBM: (592+35
)*438*129 (3U)
(1)
TWIN PRO3 :
4÷10 k/EBM : 589 x 225 x 452
6÷10 k B1 : 353,2 x 225 x 452
< 3000 m (use derating over 1 km, the load must be reduced by 1% every 100 m)
Low speed fans:
< 40 dB for 4/6 k, < 45 dB for 8 k/10 k
Medium speed fans:
< 45 dB for 4/6k, < 50 dB for 8k/10k
High speed fans:
< 50 dB for 4/6k, < 55 dB for 8k/10k
Ultra-high speed fans:
< 55 dB for 4/6k, < 60 dB for 8k/10k
EN-IEC 62040-2: 2016, EN-IEC 62040-2: 2018
TWIN PRO3 / RT3
6
6 B1
8
25 A/100 ms
36 A/100 ms
192 V DC
16 PCS (PRO3 "STD" / RT3 "EBM" models)
32 PCS (PRO3 "EBM" models)
NO
16 x 12 V @ 9 Ah
6
0 ÷ 300
Yes
Yes
Optimised Battery Management (OBM)
4 A (adjustable
2 A (adjustable 0 ÷ 4 A)
0 ÷ 12 A)
NO
3 hours at 90%
Yes (60% power reduction)
LCD dot matrix
Multi language
USB 2.0 with HID power device
Yes (DB9)
Yes
Optional (WLAN dongle)
RJ45 (Nimbus cloud)
WinPower, IoT (downloadable)
IP20
Yes, only for TWIN PRO3 models
0ºC ÷ +50ºC (50% derating at 40ºC)
-15ºC ÷ +40ºC
-25ºC ÷ +55ºC
0 ÷ 95% non-condensing
EN-IEC 62040-1
EN-IEC 62040-3
CE, UKCA, CMIM
ISO 9001 and ISO 140001
10
10 B1
113 A for 200 ms max.
54 A/100 ms
110 A
NO
4 A (adjustable
0 ÷ 12 A)
NO
SALICRU