7.5. MAIN SCREEN.
Fig. 61. Status screens.
Once the UPS has been started up, the system will enter this
main screen by default. Each screen is automatically displayed for
3 seconds.
Press
to block and
display.
Battery
status
Fig. 62. Description of the LCD display.
USER MANUAL
to automatically restore the
Operating
IoT
status
status
Load/unit
status
The following table describes the UPS status information.
Operating status
Cause
Standby mode
On-Line mode
1 beep every
4 sec.: Battery
mode
1 beep every
sec.: Battery
mode with
low batt.
HE (high
efficiency)
Frequency
converter
(CVCF)
Bypass mode
Battery test
Battery fault
Overload
Fault mode
Parallel mode
IoT enabled
IoT disabled
Tab. 18. Information about the UPS status.
SLC TWIN PRO3/RT3 4÷10 kVA UNINTERRUPTIBLE POWER SUPPLIES (UPS)
Description
The UPS is off and without output
The UPS is operating normally and
protecting the loads
A mains failure has occurred and the
UPS supplies the loads via the battery.
Prepare the loads for shutdown
This warning is approximate and
the actual shutdown time may vary
significantly.
Indicates that the device is supplying
voltage via the Bypass (ECO mode)
1. The function can be enabled via the
LCD screen settings or the software
(Winpower, etc.).
2. Please note that the transfer time
of the UPS in high efficiency (HE)
mode to Battery mode is about 10 ms,
which may be too long time for certain
critical loads
The UPS would work with a fixed
output frequency (50 Hz or 60 Hz)
The maximum output power and
maximum load current must be reduced
to 60% in this mode
The function can be enabled via the
LCD screen settings or the software
(Winpower, etc.)
An overload or fault has occurred,
or a command has been received,
and the UPS is in Bypass mode
The UPS is running a battery test
The UPS detects that the battery is
faulty or disconnected
Certain unnecessary loads should be
disconnected to reduce the overload
Several faults have occurred. The UPS
will cut off the output or switch to
Bypass mode immediately, issuing
an alarm
The UPS works in parallel mode
The IoT connection is correct
The IoT connection is not correct
79