CABLE TYPES AND MINIMUM SECTIONS
Connection
Input voltage for 230 V AC control board
(1P+N+PE)
Signaling devices
Command and control devices
Safety devices (photocells)
When operating at 230 V and outdoors, use H05RN-F-type cables that are 60245 IEC 57 (IEC) compliant;
whereas indoors, use H05VV-F-type cables that are 60227 IEC 53 (IEC) compliant. For power supplies up to 48
V, you can use FROR 20-22 II-type cables that comply with EN 50267-2-1 (CEI).
 To connect the antenna, use the RG58 (we suggest up to 5 m).
 For paired connection and CRP, use a UTP CAT5-type cable (up to 1,000 m long).
 If cable lengths differ from those specified in the table, establish the cable sections depending on the actual
power draw of the connected devices and according to the provisions of regulation CEI EN 60204-1.
For multiple, sequential loads along the same line, the dimensions on the table need to be recalculated
according to the actual power draw and distances. For connecting products that are not contemplated in this
manual, see the literature accompanying said products
cable length
< 20 m
3G x 1.5 mm 2
2 x 0.5 mm 2
2 x 0.5 mm 2
(TX = 2 x 0.5 mm 2 )
(RX = 2 x 0.5 mm 2 )
20 < 30 m
3G x 2.5 mm 2