7.
Installation and electrical connection
All installation and electrical work may only
be carried out by qualified personnel and in
compliance with local codes and regulations!
WARNING! Risk of severe injury!
The applicable regulations for the prevention of
accidents must be complied with.
WARNING! Risk of electrical shock!
Danger from electric current must be eliminated.
7.1
Upon receipt of the product
Unpack the pump and recycle or dispose of the
packaging in an environmentally responsible
manner.
7.2
Installation
The pump must be installed in a dry, wellventi-
lated location free of frost.
CAUTION! Risk of damage to the pump!
The presence of foreign matter or impurities in
the pump housing may affect the functioning of
the product.
• It is recommended to perform any welding and
soldering work before installing the pump.
• Rinse the circuit completely before installing and
commissioning the pump.
- The pump must be installed in a place easy to
access for the purposes of inspection or replace-
ment.
- For heavy pumps, install a lifting hook
(Fig. 2, pos. 10) above the pump to facilitate
its disassembly.
WARNING!
Risk of accident due to hot
The pump must be installed in such a way that
no one can touch the hot surfaces of the product
when it is in operation.
- Install the pump in a dry and frostfree place on
a flat concrete block using appropriate screws.
If possible, use an insulating material under the
concrete block (cork or reinforced rubber) to
avoid any noise and vibration transmission into
the unit.
WARNING! Risk of tipping!
Ensure that the pump is correctly secured to the
ground.
- The pump must be installed in an easily accessi-
ble location to facilitate inspection and mainte-
nance work. The pump must always be installed
perfectly upright on a concrete baseplate.
CAUTION! Risk of foreign matter in the pump!
Ensure that all blanking plugs are removed from
the pump housing before installation.
NOTICE: All pumps are factorytested for their
hydraulic properties and may therefore contain
a small amount of residual water. For hygiene
purposes, it is recommended to rinse the pump
before installing it in any potable water supply.
Installation and operating instructions –
surfaces!
Helix EXCEL 2461016
- For installation and connection dimensions see
section 5.2.
- Lift the pump only with appropriate lifting devic-
es and suitable hoists and slings in compliance
with lifting regulations.
WARNING!
Risk of
tipping!
There is a high risk of tipping due to the high
centre of gravity, especially for larger pumps. Take
special care over the safe fixation of the pump
when handling.
WARNING!
Risk of
tipping!
Use integrated lifting hooks only if they are not
damaged (e.g. by corrosion). Replace them if
required.
WARNING!
Risk of
tipping!
Never lift the complete pump using the motor
hooks as these are designed to lift the motor only.
- Motors are equipped with drain holes for con-
densed water (under the motor) that are sealed
at the factory using plastic plugs to ensure IP55
protection. If used in air-conditioning or cooling
systems, remove these plugs to allow condensa-
tion water to drain.
English