Installation and Wiring Instructions for the SOLO Plus Bathroom Extract Fan.
IMPORTANT:
READ THESE INSTRUCTIONS
BEFORE COMMENCING THE
INSTALLATION
DO NOT install this product in areas where the following may be present or occur:
Excessive oil or a grease laden atmosphere.
Corrosive or flammable gases, liquids or vapours.
Ambient temperatures higher than 40°C or less than –5°C.
Possible obstructions which would hinder the access or removal of the Fan.
SAFETY AND GUIDANCE NOTES
A. All wiring to be in accordance with the current I.E.E. Regulations, or the appropriate standards of your country
and MUST be installed by a suitably qualified person.
B. The Fan should be provided with a local isolator switch capable of disconnecting all poles, having a contact
separation of at least 3mm.
C. Ensure that the mains supply (Voltage, Frequency, and Phase) complies with the rating label.
D. The Fan should only be used in conjunction with the appropriate Vent-Axia products.
E. It is recommended that the connection to the fan connector terminals is made with flexible cable.
F. When the Fan is used to remove air from a room containing a fuel-burning appliance, ensure that the air
replacement is adequate for both the fan and the fuel-burning appliance.
G. The Fan should not be used where it is liable to be subject to direct water spray for prolonged periods of time.
H. Where ducted Fans are used to handle moisture-laden air, a condensation trap should be fitted. Horizontal
ducts should be arranged to slope slightly downwards away from the Fan.
I. This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of knowledge, unless they have been given supervison or instruction concerning use of the
appliance by a person responsible for their safety.
J. Children should be supervised to ensure that they do not play with the appliance.
K. The Fan can be used in tropical climates.
DESCRIPTION
As standard, the SOLO Plus is suitable for panel/wall installations, flush or surface mounting, either in a horizontal
or vertical plane. 100mm ducting (flexible or straight) can be attached using the supplied adjustable spigot,
providing rear or side exit options. Adaptors for System 25 and System 50 ducting can be used in conjunction with
the adjustable spigot. For wall installations a Wall Kit (25 41 02 White / 25 41 00 Brown) can be used. Please see
our catalogue or web site (www.vent-axia.com) for more information on System 25/50 and for alternative ducting
and termination options.
A. INSTALLATION
PANEL MOUNTING (Surface)
1. Cut a 105mm∅ hole through the panel, ensuring that there is sufficient space for the product to be installed
and that the filter can be removed for maintenance.
2. Removing the Front Assembly [A]. Firstly remove the Filter [B] (fig. 2.) by squeezing the clips and pulling. Insert
a small bladed screwdriver into the slots as shown in figure 3 and push gently to release. Lift the front
assembly slowly from the bottom edge ensuring not to damage the sensor cable (TM model only) attached to
the front assembly and Base Housing [C] (fig. 3/4/11.). IMPORTANT: The cable for the PIR sensor (TM
model only) is not connected as supplied but can be removed by carefully unclipping the cable header
from the Front Assembly [A].
3. Remove the Spigot Ring [G] from inside the carton and clip over the Spigot Adaptor [E] making sure the lip on
the Spigot Ring locates firmly inside the groove on the Spigot Adaptor (fig. 6.). Ensure that the Spigot Adaptor
is firmly located onto the Base Housing and the shutter is still securely fastened and fully functional.
4. Set-up the appropriate speed selection and other features as outlined in Section B SETUP.
5. Attach the ducting to the Spigot and locate into the hole in the panel ensuring the Skirt [H] is located correctly
into the Base Housing. Secure into position using appropriate fixtures (fig. 7.).
6. Ensure the Impeller rotates freely.
7. Select and follow the appropriate wiring diagram in Section C WIRING.
8. Replace the Front Assembly ensuring that the PIR sensor cable (TM model only) is reconnected to the PIR
sensor PCB (fig. 11.).
9. Switch the mains power supply on and check the fan is operating correctly.