Télécharger Imprimer la page

Energizer eZV Serie Guide De L'utilisateur page 26

Masquer les pouces Voir aussi pour eZV Serie:

Publicité

Les langues disponibles

Les langues disponibles

5.4 AC PARALLEL OPERATION
WARNING!
Do not start the generators before connecting the parallel cable.
If the cable is connected while one generator is running it will be
overloaded.
WARNING!
Only connect two Energizer
with the Energizer i-Series parallel kit. Attempting to connect a
different brand or model in parallel with your generator will void your
warranty and could cause bodily harm.
NOTE
  For continuous operation do not exceed the combined rated power.
  Stop the engine before connecting or removing the parallel cable.
  For single unit operation the parallel cable must be removed.
  The onboard generator outlets will not function when the parallel kit is
plugged in.
1.
Make sure both generators are OFF.
2.
Connect the two parallel connectors to the two parallel sockets of each
generator.
3.
Attach the ground wire to the ground terminal on the first inverter generator
then connect the second ground wire to the second inverter generator.
4.
Start each engine according to 'Starting the Engine'.
5.
Confirm appliances are turned off, then connect the appliance to the
parallel kit.
6.
Turn on the appliance.
a nk•• F i l te r••
i-Series inverter generators in parallel
®
19

Publicité

loading

Ce manuel est également adapté pour:

Ezv2200i