Basic device

The basic device consists of a ready-to-use heat pump for indoor
installation, complete with sheet metal casing, control panel and
integrated heat pump manager. The refrigerant circuit is hermet-
ically sealed. It contains the Kyoto protocol approved refrigerant
R410A with a GWP value of 2088. It is CFC-free, does not de-
plete ozone and is non-flammable.
All components required for the operation of the heat pump are
located in the control box. An external temperature sensor in-
cluding fixing accessories, a dirt trap and a flow rate switch, is
supplied with the heat pump. The voltage supply for the load and
control current must be provided by the customer.
The well water pump (to be provided by the customer) must be
controlled via the switch box. It must be equipped with a motor
protection device, if required.
The customer must provide hydraulic components for the well
water circuit.
1)
Control
2)
Evaporator
3)
Liquefier
4)
Compressor
5)
Transport securing devices
6)
Hot water liquefier
EN-4
4

Accessories

4.1 Connecting Flanges

The use of flat-sealing connecting flanges allows the unit, as an
option, to be connected by means of flanges.
4.2 External four-way reversing
valve, Water circuit side
The external four-way reversing valve (Y12) enables optimised
heating and cooling operation of the reversible water-to-water
heat pump. The reversal of the flow direction ensures an opti-
mum flow through the heat exchanger on the secondary side,
both in heating operation and in the opposite direction in cooling
operation. The electrical actuator required for automatic switch-
ing is controlled by the heat pump manager. (Max. permissible
switching current 2A).
If the external four-way reversing valve is not used, the heat out-
puts and the COPs are reduced as specified in the device infor-
mation. With heating-only operation without an external four-way
valve, the hydraulic connection should be carried out such that
the heat exchanger is loaded in the opposite direction (observe
note in section 7.2 „Connection on heating and hot water side").
The external four-way reversing valve with a set time of max. 60
seconds, which is available as special accessory, ensures
switching of the water flow over the complete range of operating
temperatures without any mixing losses.
The hydraulic and electrical circuit diagrams in the appendix
show the basic design. Detailed installation instructions are pro-
vided with the four-way reversing valve.

4.3 Remote control

A remote control adds convenience and is available as a special
accessory. Operation and menu navigation are identical to those
of the heat pump manager. Connection takes place via an inter-
face (special accessories) with RJ 12 Western plug.
NOTE
In the case of heating controllers with a removable operating element,
this can also be used directly as a remote control.