EN
2.
Fit foam strip supplied to connector in
centre.
The foam strip must be fitted to the
i
ECA 100 ipro RCH such that the
units do not draw in any unwanted air
from outside.
8. Mounting
8.1 Housinginstallation
1.
Insert housing [1] into wall breakthrough/
wall sleeve (TOP must be at top).
2.
Align housing horizontally and mark the
two dowel holes (arrows, fig. above).
3.
Remove housing [1], drill M6 dowel holes
with a Ø of 6 mm and insert dowels.
4.
Push cable grommet [3] carefully out of
housing and remove.
24
Danger of short-circuits and
NOTICE
damage to the unit. Water will
penetrate if the power cable is
incorrectly fed into the fan
housing or if the cable grom-
met is not fitted correctly.
Cut off cable grommet cap [3]
such that the cable grommet fits
tightly round the power cable.
Cut a maximum of 5 mm off the
cap (power cable can bend
better and electronics cover [4]
can be positioned correctly).
Fit cable grommet [3] correctly,
seal on both sides if required.
5.
Insert cable grommet into housing.
Feed power cable into the connection
i
area such that the cable grommet fits
around the cable sheathing comple-
tely and does not penetrate too far
into the connection area.
8.2 Electrical connection
Danger to life from electric
shock.
Switch the mains fuse off.
DANGER
Risk of damage to unit in the
NOTICE
event of short-circuits.
Insulate PE conductor and
individual cable cores that are
not required.
Always note the relevant specifica-
i
tions for electrical installations and
when installing equipment. In Germany
particular attention must be paid to
the DIN VDE 0100 and the corres-
pondding parts.
Permitted mains cable:
i
min. 3 x 1.5 mm².