9.2. Troubleshooting Faults
When the troubleshooting below calls for "power cycle" here is the
procedure: turn off power to the motor, wait 30 seconds, turn power
back on to the motor to restart. Note that the drive automatically retries
after the 30 second wait time. Number of retries is not limited; drive will
retry until the fault condition is cleared and a successful restart is
achieved..
Fault
Description
Motor soft-
Sensorless
ware fault
loop in software
lasted too long
Under Voltage
DC bus voltage
falls below
the threshold
voltage
Over Voltage
DC bus voltage
exceeds the
threshold
voltage
Over Tempera-
IPM tempera-
ture
ture is above
threshold
Speed Feed-
Measured
back
speed does not
match refer-
ence speed
Start Up
Open to close
loop transition
failed
Loss of output
Disconnection
phase
of motor phase/
winding
Over current
Hardware over
voltage or short
circuit fault
UL Safety fault
One of the UL
safety core
faults
Internal Com-
Internal com-
munication
munication
Loss
between micro
lers is lost
Software Error
Motor firm-
ware error
10. Recycling/disposal
The protection of the environment and the conservation of resources
are important issues for Nicotra Gebhardt. We therefore pay attention to
sustainable, environmentally friendly designs, as well as technical
safety and health protection when developing our fans. When disposing
of components or waste, please observe the applicable country-specific
legal regulations.
10.1. Disassembly
The disassembly of the product must be performed or monitored by
specialist personnel. The disassembly process should be prepared as
follows:
10
© 2023 Regal Rexnord Corporation. All Rights Reserved.
Possible Remedy
Power cycle to reset drive
Check line voltage to verify it is
within 10% of nameplate voltage
Check line voltage to verify it is
within 10% of nameplate voltage
Turn off motor and remove power
to allow drive to cool. Verify that
the chimney of the drive is not
blocked. Restart and retry.
Check if fan is loose and retight-
en. Check if shaft is physically
locked and try to free. Restart
and retry
Check if fan is loose and retight-
en. Check if shaft is physically
locked and try to free. Restart
and retry
Please contact your service
partner
Power cycle and try again. If
problem persists, replace motor
UL safety core faults occur for
various reasons such as a locked
rotor or an overloaded situation.
Turn off motor and verify the
shaft is not locked and retry.
Power cycling can reset the fault
Power cycle and try again. If
problem persists, replace motor
Power cycle and try again. If
problem persists, replace motor
XXXXXXXXXX • Format# XXXXXX R1
•
Disconnect the machine from the mains and remove all cables.
•
Transport the machine to a suitable location for the disassembly
process.
WARNING
The products include certain components that are quite heavy. These
can fall down during disassembly. This may cause serious physical
injury, death and material damage. Secure machine parts that are to
be disassembled to prevent them from falling down.
10.2. Component disposal/recycling
The machine is made predominantly from metallic materials. These are
fully recyclable. Please separate the components into the following
categories:
•
Steel and iron, aluminium, non-ferrous metal, insulating
materials, cables and leads
•
Electronic scrap (where present), plastics
•
Electronic components must be disposed of as electronic scrap
11. Service
We offer all of our partners the following service:
Mobile customer service
Phone +49 (0)7942 101 0
Fax +49 (0)7942 101 170
info.ng.de@regalrexnord.com
www.nicotra-gebhardt.com
12. Manufacturer's notification
Our products are manufactured in compliance with applicable
international standards and regulations. If you have questions regarding
the use of our products, or if you are planning a special application,
please contact us.
U L C E RT I F I E D
U L F I L E N U M B E R :
X D N W 2 . E 3 0 6 12 3 –
E L E C T R O N I C A L LY P R OT E C T E D
M OTO R S C O M P O N E NT
E N