PF-6
PROGRAMMING
This function is used to calibrate
the air inlet opening for each
calibration step. A step is
created each time a new stage
is activated or whenever the
speed on a variable speed stage
reaches
100%
activating a new stage.
Settings
The step number is displayed as "S.X" where X is the step
number (0 to 28), alternating with the air inlet opening. When
the step correspond to a speed of 100 % on a variable stage
with no new stage activated, "Hi" is displayed in the alternating
sequence and the step number is not incremented.
When calibrating, use the adjustment knob to manually adjust
the opening value : OFF to stop adjusting, CLO to close, OPN
to open and AUT to retrieve the previously calibrated position.
Press the push-button to calibrate the next step. The last step
is the over-opening stage.
Press the push-button after the over-opening stage to end the
calibration. "END" is displayed. If this is not done, none of the
calibration steps will be stored in memory. Set internal switch
#7 to OFF to end the calibration.
After a calibration, the opening of each point can be edited.
26
PF-6.rev.14