3. When finished adjusting, use the adjustment knob to return to the off
position.
4. Press the push-button on the primary PF-6 unit to record air inlet
positions for all PF-6 units (note that the push-button on slave units is
disabled during calibration).
5. The temperature controller increases the temperature to the next
step. A new step is created either when a new stage turns on or
when a variable stage reaches maximum speed. When the second
case occurs, the step value is not incremented and the PF-6 displays
"Hi".
6. Repeat steps 2, 3 and 4 until the last stage on the controller is
reached.
7. When the last stage has been calibrated, the temperature controller
increases the temperature to 120°F to calibrate the over-opening
step. Use the adjustment knob to manually adjust the opening value
on each PF-6 unit for the over-opening step – CLO to close, OPN to
open, AUT to retrieve the previously calibrated position, and OFF to
finish adjusting.
Temperature
Set Point
8. Press the push-button on the primary PF-6 to finish the calibration.
If this is not done, none of the calibrated openings will be saved.
Each PF-6 displays End.
9. Set internal switch #7 to OFF on all PF-6 units.
22
PF-6.rev.14
Last Step
Inlet Opening
CONTROLLER STEP
Over-Opening
Inlet Opening
OVER-OPENING
Temperature
DIFFERENTIAL