6. VERIFY PF-6 OPERATION
Power the PF-6 and set the function selector to MANUAL MODE
position. Use the adjustment knob to select OPN to open, CLO to
close or OFF to stop the winch.
Verify motor operation:
Open and close the air inlet panels using the open-close switch.
The air inlet panels should open when the switch is set to OPEN
and close when the switch is set to CLOSE. If the air inlet panels
move the opposite way, the motor operates in the wrong
direction. Turn off the power and reverse the wires connected
to terminal #3 and #4. Verify that the motor now operates in
the right direction.
Verify limit positions of air inlet panels:
Fully close the air inlet panels using the open-close switch. Adjust
the power unit limit switch to this position in order to prevent the
power unit from closing further. Fully open the air inlet panels
using the open-close switch. Adjust the power unit limit switch
to this position in order to prevent the power unit from opening
further.