CONTROLLER FUNCTIONS
ACTUAL OPENING
This function gives a readout of the
current air inlet opening as a
percentage from 0 % to 100 %
(limit values are determined during
the calibration). This function also
allows to modify the needed
hysteresis value to activate the
actuator. Minimum and maximum opening values can also be displayed.
Note that this function is not available during calibration.
Settings
The current opening is displayed as a percentage.
Turn the adjustment knob one notch to the right. The maximum
value is displayed alternating with the letters "Hi".
Turn the adjustment knob one notch to the left. The current
opening is displayed.
Turn the adjustment knob one notch to the left. The minimum
value is displayed, alternating with the letters "Lo".
Press and hold the push-button during 5 seconds. The hysteresis
is displayed alternating with the letters "HYS".
Use the adjustment knob to adjust the hysteresis to the desired
value.
Note :
If you let the display flash for more than 10 seconds, the controller
resets the minimum and maximum opening values currently in memory.
In other words, the two values are reset to the current opening value. To
avoid resetting minimum and maximum values, return to the current
opening display using the adjustment knob (clockwise or
counterclockwise) before the 10 second delay has elapsed.
23
PF-6.rev.14